Specifications

NEW!
TRANSDUCERS
1442
NEW!
TRANSDUCERS
23
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
kele.com888-397-5353 USA
March 2014
1. Set output OUT jumper to V or MA as desired.
2. Set INPUT jumpers for type and range of input signal
present. See “Input Jumpers” table above.
3. If using the reference output for sensor excitation, set the
two REF jumpers for the proper output type and value.
Choices are 1.2V, 5V, 10V, 1.2 mA, 5 mA, 10 mA. If not using
the reference output, jumper as a voltage output.
4. Set action ACT jumper to direct D or reverse R as desired.
5. Set span jumper SPN to LO. Turn SPAN pot clockwise 25
turns.
6. Remove both Z1 jumpers. Trim ZERO 1 pot for minimum
desired output value. Presence/absence of input signal has
no effect on this adjustment.
7. Reinstall both Z1 jumpers. Set Z2 jumper to LO position.
8. Apply an input signal value that is to produce minimum
output. Trim ZERO 2 pot for minimum output value (same
value set in step 6). If desired value cannot be achieved,
remove Z2 jumper and trim ZERO 2 pot again. If desired
value is still not achieved, place Z2 jumper in HI position and
trim ZERO 2 pot again.
9. Apply input signal value that is to produce maximum output.
Trim SPAN pot for maximum output value. If SPAN pot does
not go high enough, move the SPN jumper from LO position
to HI position.
10. Repeat steps 8 and 9 until both minimum and maximum
output values are correct. Typically, just one more pass is
sufficient.
11. Apply a midpoint input signal. Verify that output goes to
center of output range.
UNIVERSAL ANALOG TRANSDUCERS
UAT-1, UAT-2 SERIES
ORDERING INFORMATION
ZERO 1
ZERO 2
SPAN
Z1
Z2
SPN
ACT
INPUT
OUT
SIG OUT
24V PWR
COM
REF OUT
SIG IN
UAT- 1
UAT- 2
0-18 VDC or
0-20 mA Output
Jumper-Selectable,
Adjustable
24 VAC/VDC
Power Supply
COM
SIG
IN
REF
OUT
0-20 VDC or
0-40 mA Input
Jumper-Selectable,
Adjustable
(no connection required
to REF OUT terminal)
COM
SIG IN
COM SIG IN
REF OUT
(VOLTS)
Three-Wire Potentiometer
100
Ω min to 10 kΩ max
element
COM SIG IN
REF OUT
(MA)
Two-Wire Variable Resistance
100
Ω min to 5 kΩ max
element
NRM NRM
HI LO
HI LO
D R
REF
1.2 5 10
MA V
X1
÷ 10
MA 10V 20V
MA V
Power LED
WIRING
CALIBRATION
UAT-1
Example: UAT-1C Universal analog transducer with factory calibration
MODEL DESCRIPTION
UAT-1 Universal analog enclosed/field-calibrated transducer
UAT-2 Universal analog snap-track mounted/field-calibrated transducer
OPTIONS
C Factory calibration (specify input and output when ordering)
47 DIN rail mounting adapter (UAT-1 only)
C
INPUT INPUT REF
SIGNAL RANGE JUMPER POSITIONS JUMPERS
0-1.09V, 55 mV min span ÷ 10 10V
0-2V, 100 mV min span ÷ 10 20V
0-10.9V, 550 mV min span x 1 10V
0-20V, 1V min span x 1 20V
0-4 mA, 0.22 mA min span ÷ 10 mA
0-40 mA, 2.2 mA min span x 1 mA V 10
Three-wire potentiometer x 1 (None) V 10
10V ref (834 min)
Three-wire potentiometer x 1 (None) V 5
5V ref (417 min)
Three-wire potentiometer x 1 (None) V 1.2
1.2V ref (100 min)
Two-wire variable resistance mA 10
10 mA ref (750 max)
Two-wire variable resistance mA 5
5 mA ref (1.5 k max)
Two-wire variable resistance mA 1.2
1.2 mA ref (5 k max)
If (ref mA) x (max )
1.09V
x 1 (None)
If (ref mA) x (max )
1.09V
÷ 10 (None)
If REF output is
required for
external sensor
excitation, jumper
for appropriate
voltage or current
source.If not used,
set jumpers to:
INPUT JUMPERS
RELATED PRODUCTS PAGE
UCM-SPA Setpoint potentiometer, 0-10 k, three-wire potentiometer on stainless steel
plate for remote mounting, 0-100% setpoint 1363