Specifications
NEW!
1431
TRANSDUCERS
TRANSDUCERS
23
WE MAKE IT EASY.
kele.com 888-397-5353 USA
March 2014
Supply Voltage None, loop powered
Input 4-20 mA, 1-9 VDC (-1 model)
Input Impedance 180Ω @ 4-20 mA, 985Ω @ 1-9 VDC
Wiring Terminations Leads with 1/2" NPT conduit
connection
Air Capacity 7,776 scim (7.6 m
3
/hr) @ 25 psig
(175 kPa) supply; 20,736 scim (20
m
3
/hr) @ 100 psig (700 kPa) supply
Pressure Range 18 psig (124 kPa) minimum, 100 psig
(690 kPa) maximum
Air Connections 1/4" FNPT with auxiliary gauge port
Air Consumption 0.1 scfm (0.2 m
3
/hr) @ midrange
Repeatability <0.5% of span
Linearity <±1% of span
Hysteresis <1% of span
Output 3-15 psig (21-103 kPa); adjustable,
can split range 3-9 or 9-15 psig
Operating Temperature -20° to 160°F (-30° to 70°C)
Dimensions 2.2"H x 4.2"W x 2.3"D
(5.5 x 10.8 x 5.7 cm)
Weight 2.1 lb (0.94 kg)
Approvals CE
Warranty 18 months
CURRENT / PNEUMATIC TRANSDUCER
T-1000
DESCRIPTION
The T-1000 Industrial-grade Current / Pneumatic
Transducer reduces a supply pressure to a regulated output
pressure that is directly proportional to a 4-20 mA input
signal. An integral pneumatic volume booster is included in
the design to provide high flow capacity up to 20,736 scim (20
m3/hr).
FEATURES
• High airflow capacity
• Wide supply pressure range
• Direct or reverse acting
• Convenient external span and zero adjustments
• Bracket included for panel or wall mounting
Zero
Span
4-20 mA
Signal
(black)
in
(cm)
(white)
Alternate Output/
Gauge Port
plugged
Supply
Air
1/4'' FNPT
Output
Air
1/4'' FNPT
WIRING / PIPING
APPLICATION
The T-1000 is calibrated at the factory for direct-acting
operation but may be used in the reverse-acting mode by
reversing the polarity of the signal leads and recalibrating.
When calibrated for reverse-acting applications, the T-1000
transducer provides a minimum of its full rated output
pressure (i.e., 15 psig/103 kPa) upon input signal failure.
The 4-20 mA input to 3-15 psig (21-103 kPa) output can be
recalibrated using zero and span adjustments to provide 3-9
psig (21-62 kPa) or 9-15 psig (62-103 kPa) output for split
ranging applications.
SPECIFICATIONS
ORDERING INFORMATION
MODEL DESCRIPTION
T-1000 Current/pneumatic transducer, 4-20 mA input, 3-15 psig (21-103 kPa) output
T-1000-1 Current/pneumatic transducer, 1-9 VDC input, 3-15 psig (21-103 kPa) output
T-1000-C Current/pneumatic transducer, 4-20 mA input, 3-15 psig (21-103 kPa) output, pre-calibrated
RELATED PRODUCTS PAGE
010115-000 DIN rail adapter for T-1000 current/pneumatic transducer
M-111 1/4" MNPT x 1/8" FNPT bushing
PG-05 Pressure gauge, 0-30 psig (10-200 kPa), 1.5" dial, 1/8" NPT center back mount 1111
T-1000