Specifications
NEW!
1427
TRANSDUCERS
TRANSDUCERS
23
WE MAKE IT EASY.
kele.com 888-397-5353 USA
March 2014
1.8
(4.6)
3.73
(9.5)
in
(cm)
3.45
(8.8)
Supply Voltage 24 VAC/VDC
Supply VA 350 mA maximum (half-wave)
Input 0-5 VDC, 0-10 VDC, 4-20 mA, tri-
state, PWM
Input Impedance 10 kΩ, VDC input; 250 Ω, 4-20 mA
input
Wiring Terminations Screw terminals
Air Capacity 333 scim (5456 cm
3
/min) @ 20 psig
(138 kPa) supply; 523 scim (8570
cm
3
/min) @ 45 psig (310 kPa) supply
Air Connections Brass barbs for 1/4" OD tubing
Air Consumption None in steady state
Maximum Pressure 45 psig (310 kPa)
Media Compatibility Clean, dry air
Minimum Tubing
Length 15 ft. (4.6 m)
Repeatability <1% full scale
Linearity <1% full scale
Hysteresis <1% full scale
Output 0-25 psig (0-175 kPa) configurable
Operating Temperature 41° to 140°F (5° to 60°C)
Operating Humidity 10 to 90% RH (non-condensing)
Dimensions 3.5"H x 3.3"W x 1.9"D
(8.5 x 8.3 x 4.6 cm)
Weight 0.8 lb (0.36 kg)
Approvals CE
Warranty 5 years
KELE UNIVERSAL ELECTRONIC / PNEUMATIC TRANSDUCERS
UCP-822A SERIES
DESCRIPTION
The Kele UCP-822A microcontroller based electronic/
pneumatic transducer incorporates high performance
poppet valve technology and low-power coils with digital
control to provide unmatched accuracy and proven reliability.
In addition to providing reliable, stable operation, the poppet
valves used in the UCP-822A consume no air. The UCP-
822A features programmable pressure ranges and an LCD
display. This universal transducer has field selectable analog
inputs for 4-20mA, voltage, tri-state, or PWM.
FEATURES
• Extended PWM and Tristate settings
• Programmable pressure output up to 25 psig
• Field-selectable signal inputs (4-20mA, voltage, tri-
state, PWM)
• LCD display for local indication of readings
• No air consumption and quiet operation
• Easy mounting with snap track housing
• Pressure loss or manual mode alarm
• Optional analog output 4-20mA or 0-10 VDC selectable
OPERATION
The UCP-822A-PL converts a selectable analog, tri-state or
PWM input to a programmable psig output (0-25 psig range).
The transducer is powered with 24 VAC/VDC. Upon a loss in
power, the UCP-822A-PL air valves remain closed, so branch
pressure will remain at the last value. The pressure loss alarm
provides a contact closure if the UCP-822A-PL is unable to
achieve the desired output within a fixed length of time. This
alarm may be changed to alarm if the transducer is set for
manual operation. The UCP-822A-AO-PL adds an analog
output for feedback of the branch pressure.
SPECIFICATIONS
DIMENSIONS