Instruction manual
6362
Technical Specifi-
c a t i o n s
Outputs
#1 Reverse acting (heating)
#2 Direct acting (cooling)
B Relay, 5 A @ 120 Vac resistive
3 A @ 240 Vac
E 0-20 mAdc, 500 ohm max.
F 4-20 mAdc, 500 ohm max.
S 20 Vdc pulsed
T Solid-state relay, 120/240 Vac,
zero voltage-switched,
1 A continuous, 10 A surge @ 25° C
Alarms
B Electromechanical relay, 5 A @ 120 Vac,
3 A @ 240 Vac
T Solid-state relay, 120/240 Vac,
zero voltage-switched,
1 A continuous, 10 A surge @ 25° C
Con-
trol Characteristics
Setpoint Limits Limited to configured range
Alarms Adjustable for high/low; selectable
process or deviation
Rate 0 to 900 seconds
Reset 0 to 3600 seconds
Cycle Time 0.2 (zero setting) to 120 seconds
Gain 0 to 400
Gain Ratio 0 to 2.0 (in 0.1 increments)
Control Hysteresis 1 to 100 units (on/off configuration)
Cool Spread, Output 2 0 to 100° F/C above setpoint (Temp.)
Spread 2, Output 2 0 to 100 units above setpoint (Process)
Technical Specifi-
c a t i o n s
Performance
Accuracy ±0.2% of full scale, ± one digit
Setpoint Accuracy 1 degree/0.1 degree
Temperature Stability 5 µV/°C max; 3 µV/°C typical
TC Cold End Tracking 0.05° C/°C ambient
Noise Rejection Common mode >100 dB
Series Mode >70 dB
Process Sampling Rate 10 Hz (100 ms)
Inputs
Thermocouple K, J, N, R, T, S,
Maximum lead resistance 100 ohms
for rated accuracy
RTD Platinum 2- and 3-wire, 100 ohms at
0° C, DIN curve standard (0.00385)
Linear 0-50 mV/10-50 mV, 0-5 V/1-5 V/
0-10 V/2-10 V, 0-20 mA/4-20 mA
Input Impedances
0-50 mV/10-50 mV: >1 M ohm ± 1%
0-5/1-5 V: 12.5 K ohm ± 1%
0-20 mA/4-20 mA: 250 ohm ± 1%
0-10 V/2-10 V: 200 K ohm