Instruction manual

5352
Digital
C o m m u n i c a t i o n s
03 Gain Output 1 Gn.o1 00 400
04 Gain Ratio 2 Gr.o2 0.0 2.0
05 Rate rAtE 00 900
06 Reset rSEt 00 3600
07 Hysteresis 1 HYS.1 01 100
08 Hysteresis 2 HYS.2 01 100
09 Spread 2 SPr.2 00 100
10 Damping dPnG 00 Low/Normal/High
11 Alarm 1 ALr1 Low Scale High Scale
12 Alarm 2 ALr2 Low Scale High Scale
13 Cycle Time 1 CY.t1 00 120
14 Cycle Time 2 CY.t2 00 120
15 Setpoint Target Time Sp.tt 00 (OFF) 100
16 Low Scale L.SCL -1999 9999
17 High Scale H.SCL -1999 9999
18 Controller ID Id.no 00 99
19 Baud Rate bAUd 300 2400
Table 3. Serial Communications Data Format
Baud Baud Parity Data Stop
Code Rate Bits Bits
3.o.7 300 Odd 7 2
6.o.7 600 Odd 7 2
12.o.7 1200 Odd 7 2
24.o.7 2400 Odd 7 2
3.n.8 300 None 8 1
6.n.8 600 None 8 1
12.n.8 1200 None 8 1
24.n.8 2400 None 8 1
Digital
C o m m u n i c a t i o n s
Table 1. Communications Parameter List
(Temperature Controller)
Parameter No. Description Display Minimum Maximum
00 Process Value nnnn Sensor Dependent
01 Setpoint nnnn Low Limit High Limit
02 Access Code Ac.Cd 00 05
03 Gain Output 1 Gn.o1 00 400
04 Gain Ratio 2 Gr.o2 0.0 2.0
05 Rate rAtE 00 900
06 Reset rSEt 00 3600
07 Heat Hysteresis H.HYS 01 100
08 Cool Hysteresis C.HYS 01 100
09 Cool Spread C.SPr 00 100
10 Damping dPnG OFF High
11 Alarm 1 ALr1 Range Dependent
12 Alarm 2 ALr2 Range Dependent
13 Cycle Time 1 CY.t1 00 120
14 Cycle Time 2 CY.t2 00 120
15 Setpoint Target Time Sp.tt 00 (OFF) 100
16 Low Setpoint Limit L.SP.L Sensor Dependent
17 High Setpoint Limit U.SP.L Sensor Dependent
18 Controller ID Id.no 00 99
19 Baud Rate bAUd 300 2400
Table 2. Communications Parameter List
(Process Controller)
Parameter No. Description Display Minimum Maximum
00 Process Value nnnn Low Scale High Scale
01 Setpoint nnnn Low Scale High Scale
02 Access Code Ac.Cd 00 05