Instruction manual

59
16. To select the Access level, the value between 0 and 2 must be
assigned as per the below table:
Access level Serial value
Full 0
Operator 1
Edit 2
17. The JbuS 122 + 123 and 124 + 125 addresses contain the strings (of
4 characters) for the product and release codes: each address
represents two characters, the most significant byte in the word
contains the ASCII code of the second.
18. To select the alarm type, the value between 0 and 6 must be
assigned as per the below table:
Alarm type Serial value
Not used 0
Absolute High active 1
Absolute Low active 2
Deviation High active 3
Deviation Low active 4
Band Out active 5
Loop Break Alarm 6
19. To select the output assignment, the value between 1 and 4 must be
assigned as per the below table:
Output assignment Serial value
OP1 1
OP2 2
OP3 3
OP4 4
20. To select the Digital input function, the value between 0 and 15 must
be assigned as per the below table:
Digital input function Serial value
Not used 0
Local/Remote 1
Auto/Manual 2
1
st
stored Setpoint 3
2
nd
stored Setpoint 4
3
rd
stored Setpoint 5
Keypad lock 6
Setpoint slopes disable 7
Measure Hold 8
Output forcing mode 9
1
st
Program selection 10
2
nd
Program selection 11
3
rd
Program selection 12
4
th
Program selection 13
Program Run/Stop 14
Program Reset 15