12.3 Word zone - Page 1 Parameters
Address
Modbus JbuS Variable Parameter
Code
Type
0 1 PV process variable - R
1 2 SP Setpoint - R
2 3 MV Main control output - R(/W)
2
3 4 SPL local Setpoint - R/W
3
4 5 SPL local Setpoint - R/W
3
5 6 Proportional band (Hysteresis ON - OFF)
P.b. (hy.)
R/W
6 7 Overshoot control
O.C.
R/W
7 8 Integral time
t.i.
R/W
8 9 Derivative time
t.d.
R/W
9 10 Cycle time
t.c.
R/W
10 11 Low range
Sc.Lo
R
11 12 High range
Sc.Hi
R
12 13 AL1 alarm threshold
A1S.P
R/W
13 14 AL2 alarm threshold
A2S.P
R/W
14 15 AL3 alarm threshold
A3S.P
R/W
15 16 AL4 alarm threshold
A4S.P
R/W
16 17 AL1 alarm high hysteresis
hy.1u
R/W
17 18 AL1 alarm low hysteresis
hy.1d
R/W
18 19 AL2 alarm high hysteresis
hy.2u
R/W
19 20 AL2 alarm low hysteresis
hy.2d
R/W
20 21 AL3 alarm high hysteresis
hy.3u
R/W
21 22 AL3 alarm low hysteresis
hy.3d
R/W
22 23 AL4 alarm high hysteresis
hy.4u
R/W
23 24 AL4 alarm low hysteresis
hy.4d
R/W
24 25 Cool proportional band
P.b. C
R/W
25 26 Cool integral time
t.i. C
R/W
26 27 Cool derivative time
t.d. C
R/W
27 28 Cool cycle time
t.c. C
R/W
28 29 Minimum output step
MU.Hy
R/W
29 30 Setpoint low limit
S.P. L
R/W
30 31 Setpoint high limit
S.P. H
R/W
31 32 Control ouput low limit
OP. L
R/W
32 33 Control output high limit
OP. H
R/W
33 34 Cool control output high limit
OP.C.H
R/W
34 35 Slope up
Sl. u
R/W
35 36 Slope down
Sl. d
R/W
36 37 Filter time constant
t.FiL
R/W
37 38 Input Shift
In.Sh
R/W
38 39 AutoTune ( 0 = Stop, 1 = Run )
tune
R/W
39 40 Adaptive Tune ( 0 = Stop, 1 = Run )
AdPt
R/W
40 41 Serial comm.s SLAVE address
Add.S
R/W
41 42 Serial comm.s SLAVE protocol
Pro.S
R/W
42 43 SLAVE baud rate
bdr.S
R/W
43 44 Remote Setpoint - R
44 45 Soft-Start activation time
St.tM
R/W
45 46 Soft-Start output value
St.OP
R/W
46 47 Control output maximum speed
OP.r
R/W
47 48 Cool Control output maximum speed
OP.rC
R/W