Instruction manual

47
12. X5000 CONTROLLER
12.1 Bit zone
Address
Modbus JbuS Variable Type
0 1 Remote status (0=LOC, 1=REM) R/W
1 2 Auto / Manual ( 0 = Auto, 1 = Manual ) R/W
2 3 AL3 alarm status (0 = OFF, 1 = ON) R
3 4 AL4 alarm status (0 = OFF, 1 = ON) R
4 5 AL1 alarm status (0 = OFF, 1 = ON) R
5 6 AL2 alarm status (0 = OFF, 1 = ON) R
6 7 Out of range ( 0 = Normal operation, 1 = Safety) R
7 8 Auto-Tune ( 0 = Disabled, 1 = Run) R
8 9 - -
9 10 Out of range ( 0 = Normal operation, 1 = Safety) R
10..11 11..12 - -
12 13 Local stored Setpoint R/W
13 14 1
st
stored Setpoint R/W
14 15 2
nd
stored Setpoint R/W
15 16 3
rd
stored Setpoint R/W
16 17 IL1 Digital input status (0=OFF, 1=ON) R
17 18 IL2 Digital input status (0=OFF, 1=ON) R
18 19 IL3 Digital input status (0=OFF, 1=ON) R
19 20 - -
20 21 Keypad lock (0=locked, 1=unlocked) R/W
21 22 Slope inhibition by serial comm.s R/W
22 23 PV Hold by serial comm.s R/W
23 24 OP1 forced status by serial comm.s(0=OFF, 1=ON) R/W
1
24 25 OP2 forced status by serial comm.s(0=OFF, 1=ON) R/W
1
25 26 OP3 forced status by serial comm.s(0=OFF, 1=ON) R/W
1
26 27 OP4 forced status by serial comm.s(0=OFF, 1=ON) R/W
1
27 28 OP5 (logic) forced status by serial comm.s(0=OFF, 1=ON) R/W
1
28 29 Output forcing value R/W
29 30 1
st
Program Run/Reset R/W
30 31 2
nd
Program Run/Reset R/W
31 32 3
rd
Program Run/Reset R/W
32 33 4
th
Program Run/Reset R/W
12.2 Read Status
Function 07 ( Read Status ) returns an eight bit status with the following
meanings:
Bit Address Variable
1 (LSB) 1 Remote status (0=LOC, 1=REM)
2 2 Auto / Manual ( 0 = Auto, 1 = Manual )
3 3 OP4 alarm status (0 = OFF, 1 = ON)
4 4 OP3 alarm status (0 = OFF, 1 = ON)
5 5 OP2 alarm status (0 = OFF, 1 = ON)
6 6 OP1 alarm status (0 = OFF, 1 = ON)
7 7 Out of range ( 0 = Normal operation, 1 = Safety)
8 (MSB) 8 Auto-Tune ( 0 = Disabled, 1 = Run)