Instruction manual
44
9. To select the re-start status of the program after a power failure, the
value between 0 and 2 must be assigned as per the below table:
Re-start status of the
program
Serial value
Continue 0
Reset 1
Ramp 2
10. To select the program time unit, the value between 0 and 2 must be
assigned as per the below table:
Program time unit Serial value
Second 0
Minute 1
Hour 2
11. To select the remote setpoint input type, the value between 0 and 4
must be assigned as per the below table:
Remote Setpoint input type Serial value
0 .. 5 V 0
1 .. 5 V 1
0 .. 10 V 2
0 .. 20 mA 3
4 .. 20 mA 4
12. To select the engineering unit, the value between 0 and 10 must be
assigned as per the below table:
Engineering unit Serial value
°C
0
°F
1
none
2
nU
3
U
4
nA
5
A
6
bar
7
PSI
8
rh
9
Ph
10
13. To select the protocol type, the value between 0 and 1 must be
assigned as per the below table:
Protocol type Serial value
Modbus 0
JbuS 1