10 11 Keypad lock (0 = locked, 1 = unlocked) R/W
11 12 Outputs lock (0 = locked, 1 = unlocked) R/W
12 13 IL1 Digital input status (0 = OFF, 1 = ON) R
13 14 IL2 Digital input status (0 = OFF, 1 = ON) R
14 15 IL3 Digital input status (0 = OFF, 1 = ON) R
15 16 - -
11.2 Read Status
Function 07 Read Status returns an eight bit status with the following
meaning:
Bit Address Variable
1 (LSB) 1 Remote
1
or program
2
status
2 2 Auto/Man (0 = Auto, 1 = Man)
3
3 3 OP4 output status (0 = OFF, 1 = ON)
4 4 OP1 output status (0 = OFF, 1 = ON)
5 5 OP2 output status (0 = OFF, 1 = ON)
6 6 OP3 output status (0 = OFF, 1 = ON)
7 7 Out of range (0 = Normal, 1 = Safety)
8 (MSB) 8 Auto-Tune (0 = OFF, 1 = Run)
Notes:
1. Available when configured as Local + Remote Setpoint only
2. Available when configured as programmed Setpoint only.
3. With Timer option only.
11.3 Word Zone - Page 1 Parameters
Address
Modbus JbuS Variable Parameter
code
Type
0 1 PV process variable
R
1 2 SP Setpoint
R/W
1
2 3 MV main control output
R(/W)
2
3 4 SPT target Setpoint
R/W
1
4 5 SPL local Setpoint
R/W
3
5 6 Proportional band (Hysteresis ON - OFF)
4
P.b. (hy.)
R/W
6 7 Overshoot control
O.C.
R/W
7 8 Integral time
t.i.
R/W
8 9 Derivative time
t.d.
R/W
9 10 Cycle time
t.c.
R/W
10 11 Low range
Sc.Lo
R
11 12 High range
Sc.Hi
R
12 13 AL2 alarm threshold
A2S.P
R/W
13 14 AL3 alarm threshold
A3S.P
R/W
14 15 AL2 alarm hysteresis
A2hy
R/W
15 16 AL3 alarm hysteresis
A3hy
R/W
16 17 Cool relative gain
r.C.Ga
R/W
17 18 Cool output hysteresis (On-OFF only)
Hy. C
R/W
18 19 -
-
-
19 20 Dead band
d.bnd
R/W
20 21 Cool cycle time
t.c. C
R/W
21 22 Cool control output high limit
OP.HC
R/W
22 23 Motor travel time
MU.tM
R/W