Instruction manual

39
18. The JbuS 122 + 123 and 124 + 125 addresses contain the strings (of
4 characters) for the product and release codes: each address
represents two characters, the most significant byte in the word
contains the ASCII code of the second.
19. These particular conditions can be activated if the corresponding
outputs are specifically configured for it.
20. To configure the digital outputs status related to the setpoint
programmer option, the value between 0 and 2 must be assigned as
per the below table:
Digital output Status Serial Value
OFF 0
Open 1
Close 2
21. To select the Run Program after Hold condition, the value between 0
and 4 must be assigned as per the below table:
Re-start status of the
program
Serial Value
Run 0
Reset 1
Ramp 2
10.6 RS-485 Configuration Dip Switch
On the RS485 board a 4 position dip Switch is provided. It enables the
correct hardware configuration of the instrument serial comm.s port as
follows:
Position On OFF
1 Polarisation +5Vcc Polarisation excluded
2 Termination set Termination excluded
3 Polarisation 0 Vcc Polarisation excluded
4 - -
11. X100 / X400 CONTROLLER
11.1 Bit Zone
Address
Modbus JbuS Variable Type
0 1 Remote status (0=LOC, 1=REM)
1
or program (0=LOC, 1=RUN)
2
R/W
1 2 Auto/Man (0 = Auto, 1 = Man)
3
R/W
2 3 OP4 digital output status (0 = OFF, 1 = ON) R
3 4 OP1 digital output status (0 = OFF, 1 = ON) R
4 5 OP2 digital output status (0 = OFF, 1 = ON) R
5 6 OP3 digital output status (0 = OFF, 1 = ON) R
6 7 Out of range (0 = Normal, 1 = Safety) R
7 8 Auto-Tune (0 = OFF, 1 = Run) R
8 9 Timer status (0 = OFF, 1 = Run)
4
R/W
9 10 Out of range (0 = Normal, 1 = Safety) R