7. To select the Output type, the value between 0 and 10 must be
assigned as per the below table:
Output Type Serial Value
Not active 0
Relay 1
Logic 5
0 .. 5 V 6
1 .. 5 V 7
0 .. 10 V 8
0 .. 20 mA 9
4 .. 20 mA 10
8. To select the retransmission content the value between 0 and 2 must
be assigned as per the below table:
Retransmission Serial Value
None 0
P.V. 1
S.P. 2
9. To select the retransmission signal, the value between 6 and 10 must
be assigned as per the below table:
Retransmission signal Serial Value
0 .. 5 V 6
1 .. 5 V 7
0 .. 10 V 8
0 .. 20 mA 9
4 .. 20 mA 10
10. To select the Setpoint type, the value between 0 and 4 must be
assigned as per the below table:
Setpoint Type Serial Value
Local only 0
Remote only 1
Local / Remote 2
Local + Trim 3
Remote + Trim 4
11. To select the Remote Setpoint signal, the value between 11 and 15
must be assigned as per the below table:
Remote Setpoint Signal Serial Value
0 .. 5 V 11
1 .. 5 V 12
0 .. 10 V 13
0 .. 20 mA 14
4 .. 20 mA 15
12. To select the Access Level, the value between 0 and 2 must be
assigned as per the below table:
Access Level Serial value
Full 0
Operator 1
Edit 2