Instruction manual
36
3. The above parameters can only be read when the Adaptive Tuning is
launched. The Td derivative time is not shown but it can be simply
calculated as the ¼ of the Ti integral time (Td = Ti/4).
4. To select the Input type, the value between 0 and 15 must be
assigned as per the below table:
Input Type Serial Value
TC J
0
TC L
1
TC K
2
TC S
3
TC R
4
TC T
5
TC Custom 6
RTD 1 7
RTD 2 8
Delta T 9
0 .. 50 mV 10
0 .. 5 V 11
1 .. 5 V 12
0 .. 10 V 13
0 .. 20 mA 14
4 .. 20 mA 15
5. To select the engineering unit, the value between 0 and 9 must be
assigned as per the below table:
Engineering Unit Serial Value
None
0
°C
1
°F
2
MA
3
MU
4
U
5
Bar
6
PSI
7
Rh
8
Ph
9
6. To select the control mode, the value between 0 and 8 must be
assigned as per the below table:
Control Mode Serial Value
On/OFF reverse action 0
On/OFF direct action 1
PID direct action 2
PID reverse action 3
Valve Drive direct action 4
Valve Drive reverse action 5
Heat/Cool Linear 6
Heat/Cool Oil 7
Heat/Cool Water 8