Installation manual
Series C Controller Configuration and Operation Manual
7-8 Athena Controls, Inc. 900M050U00
Parameter Name:
Output 1 High Limit (A4) and Output 2 High Limit (B5)
Name as Displayed
:
O1.HLO1.HLand O2.HLO2.HL
Used By:
all controllers
When Displayed:
if output type is PID
Range:
0 to 100 percent
Default:
100
Description:
Used to specify the highest percentage used for the output in
both manual and normal (automatic) modes.
Effect on Other
Parameters:
No effect on other configuration parameters. However, it limits
the allowable range for the fixed output percent in manual mode.