7.4 Configuring Output Parameters for PID Control
7.4.1 Choosing the Output Action for PID Control
When an output is used for PID control, it can be either direct or reverse acting.
When the PID output action is configured for reverse action (heating
applications), the proportional band is initially applied below the setpoint.
When the PID output action is configured for direct action (cooling applications),
the proportional band is initially applied above the setpoint.
Parameter Name:
Output 1 Action (95) and Output 2 Action (A6)
Name as Displayed
:
O1.ACO1.AC and O2.ACO2.AC
Used By:
all controllers
When Displayed:
if output type is on/off or PID
Choices:
dirdir direct
rErE reverse
Default:
output 1: reverse
output 2: direct
Description:
Used to specify whether the output will be direct-acting or
reverse-acting.