5. Input Parameters – Required
5.1 Introduction
If you plan to use a thermocouple or RTD input and a unit of measure other than
Fahrenheit (the default), the first step is changing the unit of measure to Celsius or
Kelvin.
Otherwise, the first step when configuring a controller is specifying the input type using
the InPInP (input) menu, then specifying the bias (if any) to be applied to the input, scaling
the input (linear types only), specifying the setpoint range, and setting an input filter value
(if any).
This menu is available only when the security access level is set to CnF9CnF9 (configuration)
or FACtFACt (factory).
21
5.2 Calibration Must Be Appropriate for Input Type
You do not have to calibrate every new controller. When a controller was ordered,
you specified an input type for which the unit was calibrated at the factory. This is not the
specific type chosen with the input menu tYPEtYPE (type) parameter, such as J
thermocouple, or 0 to 20 mA linear. In the context of ordering the controller, “type” refers
to these choices:
RTD
compressed RTD
thermocouple
millivolt linear
volt linear
current linear input.
The controller was calibrated at the factory for the type of input specified. If you use the
controller with a different type of input, you must recalibrate as described in Section 18
unless you ordered the “Calibrate All” input option.
22
For example, if you specified when you ordered the controller that you planned to use a
thermocouple as the sensor, then you can use the input menu tYPEtYPE (type) parameter to
choose any thermocouple type: B, C, E, J, K, N, NNM, R, S, T, or Platinel II. The
controller will be calibrated appropriately at the factory. However, if you ordered
thermocouple calibration, but decide to use the controller with an RTD sensor, then you
should recalibrate before using the controller.
21
The access level in all new 16C, 18C, and 25C controllers is set to CnF9CnF9 at the factory. If you cannot
see the input menu, the access level has been changed to a more restrictive level. Instructions for
changing the access level are in Section 17.
22
To determine whether the controller in hand was calibrated at the factory for all input types, check the
model number on the label on the controller. The meaning of each character in the model number is in
the installation manual supplied with the controller.