Installation manual

Series C Controller Configuration and Operation Manual
3-4 Athena Controls, Inc. 900M050U00
b) Press the key to write the cycle time value to the controller’s database and
display the next parameter O1.LLO1.LL (output 1 low limit). Most applications use the
default value.
c) Press the key to accept the output 1 low limit default and display the next
parameter O1.HLO1.HL (output 1 high limit). Most applications use the default value.
6. Specify the output type for output 2.
Important: If only one output is PID, change output 2 from the default PidPid, to one of
the other choices: on.oFon.oF (on/off), AlrAlr (alarm), or OFFOFF.
a) Press the key to display the O2.tYO2.tY (output 2 type) parameter, alternating with
its current setting.
b) The default for output 2 is PID. If PID is not right for your application, use the
or arrow key to display the desired output type.
c) Press the key to make this selection. What parameter you see next depends
on the output 2 type you selected.
If you use PID or on/off control for output 2, you will see O2.ACO2.AC (output 2
action). Go on to step 7 below.
If you set output 2 to off, you will again see the O1.tYO1.tY (output 1 type)
parameter. Go to step 9.
If you plan to use output 2 for alarm annunciation (available on 16C only),
you will see 02.AA02.AA (output 2 alarm action). Read 7.5 and configure the
output alarm parameters before returning to step 9 in this section.
7. Specify the output 2 action for PID or on/off control.
a) When the O2.ACO2.AC parameter is on display, use the or keys to display the
action for your application.
b) Press the key once to write the action choice to the database. What
parameter you see next depends on the choice you make for the output 2 type.
If output 2 is PID, the next parameter, O2.CYO2.CY (output 2 cycle time) will be
displayed.
If output 2 is on/off, configuration of output 2 has been completed, and O1.tYO1.tY
will again be displayed. Go to step 9.
8. Specify the output 2 cycle time for PID control.
a) When the O2.CYO2.CY parameter is on display, use the and keys to display
the appropriate time for your application and the output hardware (see step 5a
above).
b) Press the key to write the value to the controller’s database and display the
next parameter O2.LLO2.LL (output 2 low limit). Most applications use the default
value.