Installation manual

Series C Controller Configuration and Operation Manual
2-12 Athena Controls, Inc. 900M050U00
5. To write the output 1 percentage to the controller’s database, press the key
(briefly). The controller will begin to use the specified fixed output percentage. (The
transition from automatic PID to the manual percentage will be “bumpless”.) The
lower line display will change to Pct2Pct2, alternating with the current value for output 2.
6. Use the and keys to change the manual output 2 value displayed to the
desired percentage.
7. To write the output 2 percentage to the controller’s database, press the key
(briefly). The controller will begin to use the specified fixed output percentage.
8. The controller will remain in manual mode until you press and hold the key to
display CtrLCtrL and FOPFOP, then change to one of the other modes as described above
and below.