Alarms configured using the output menu and alarms configured using the alarm menu
are independent of one another. For example, suppose you have a 16C controller that is
equipped with two standard outputs (one analog, the other a relay) and an alarm output
card with two more relays. You could use the output menu to configure the analog output
for PID control and the relay output as a latched process alarm. In addition, you could
use the alarm menu to configure LED A1 to light and optional alarm output relay 1 to go
to the alarm state for a high deviation alarm, while A2 and optional alarm output 2 could
annunciate a low deviation alarm condition.