14.7 Configuring Auxiliary Output Parameters
14.7.1 Introduction
If the card type is A.OutA.Out, then the A.OutA.Out menu is displayed.
14.7.2 Selecting the Value to be Transmitted
Parameter Name
: Auxiliary Output Variable (G1)
Name as Displayed
:
Out.UOut.U
Used By:
all except 1ZC
When Displayed:
if the card type is auxiliary analog output
Choices:
St.PtSt.Pt setpoint
ProcProc process value
Default:
process value
Description:
Used to choose the value to be transmitted by the auxiliary
analog output.
14.7.3 Scaling the Auxiliary Analog Output
Parameter Name
: Auxiliary Output Scale Low (G2) and Auxiliary Output Scale
High (G3)
Name as Displayed:
SCL.L SCL.L and SCL.HSCL.H
Used By:
all except 1ZC
When Displayed:
if the card type is auxiliary analog output
Range:
RTD and thermocouple input types: sensor low limit to sensor
high limit
linear input types: limited by the scaling defined for the input
using the SCL.LSCL.L and SCL.HSCL.H parameters in the InPInP (input) menu
(See Note 1 below.)
Default:
scale low: –328
scale high: 1400
Description:
Used to specify the PV or SV represented by the lowest (SCL.LSCL.L)
and highest (SCL.HSCL.H) possible auxiliary analog output signal.
Note 1: The range is reduced when a linear input is used and the value of the dSPLdSPL
(display) menu dEC.PdEC.P (decimal position) parameter is not 0 (zero). See 4.3.2 for more
information about the effect of a linear input on numerical ranges.