14-8 Athena Controls, Inc. 900M050U00
14.6 Configuring Serial Communication Parameters for Athena
Plus Protocol
14.6.1 Introduction
The items that appear on the SerLSerL (serial) menu in controllers that support Athena Plus
protocol are different from the SerLSerL menu items displayed if the controller supports the
MODBUS protocol. The Multi-Comm User’s Guide contains more information about
configuring a controller to communicate with the Multi-Comm host over an RS-232 or
RS-485 network. We recommend that you consult that manual before setting up your
Multi-Comm network and configuring these communication parameters.
14.6.2 Assigning a Unique Controller Address When Athena Plus is Used
Parameter Name
:
Controller ID Number (D5)
Name as Displayed:
Id.noId.no
Used By:
all except 1ZC (See Note 1 below.)
When Displayed:
if the card type is serial
Range:
1 to 255
Default:
1
Description:
Used to assign a unique address to each controller on the
RS-485 network. (RS-232 communication is one-to-one, so the
default address 1 is always OK for RS-232 controllers.)
Note 1: The address for a 1ZC controller is set using DIP switches as described in the
manual provided with the controller.
14.6.3 Selecting the Baud Rate Applicable to Athena Plus Communications
Parameter Name
: Baud Rate (D6)
Name as Displayed
:
baUdbaUd
Used By:
all
When Displayed:
if the card type is serial
Choices:
300
600
1200
2400
4800
9600
Default:
16C, 18C, 25C: 9600
1ZC: 2400
Description:
Used to select the baud rate.