Installation manual

900M050U00 Athena Controls, Inc. 12-1
12. Supervisor Parameters – Recommended
12.1 Introduction
You can use the SUPrSUPr (supervisor) menu to specify the output percentages to be used if
the controller detects a problem with the process input (failsafe values), and the length of
the time period during which the input should change in response to output action if the
input is working normally (loop break time).
You can also use this menu to see the highest and lowest process value received by the
controller since the controller was powered up.
The supervisor menu can also be used to set the values of all the configuration
parameters back to their factory defaults in 16C, 18C, and 25C models. The calibration
of the controller will not be affected when the defaults are set back to their factory
defaults.
The supervisor menu is available only when the security access level is set to CnF9CnF9
(configuration) or FACtFACt (factory).
37
Item Parameter Name When Displayed
FS.01FS.01
Output 1 Failsafe Output
Percentage
if output 1 type is PID or on/off
FS.02FS.02
Output 2 Failsafe Output
Percentage
if output 2 type is PID or on/off
L.br.tL.br.t
Loop Break Time always
HI.rdHI.rd
Highest Reading always
LO.rdLO.rd
Lowest Reading always
Ld.dpLd.dp
Load Default Parameter Values always
37
The access level in all new 16C, 18C, and 25C controllers is set to CnF9CnF9 at the factory. If you cannot
see the supervisor menu, the access level has been changed to a more restrictive level. Instructions for
changing the access level are in Section 17.