Installation manual
Ramp/Soak Recipe Parameters
900M050U00 Athena Controls, Inc. 11-11
11.4.3 Configuring Individual Recipe Segments
11.4.3.1 Specifying the Ramp Time for Each Step of a Multi-Step Recipe
Parameter Name
: Ramp Time 1, Ramp Time 2, etc. through Ramp Time 8
(42 through 49)
Name as Displayed
:
rt1rt1, rt2rt2 through rt8rt8
Used By:
all controllers
When Displayed:
if the recipe option is eight-segment r/s recipe
Range:
0 to 9999 minutes
Default:
0
Description:
Used to specify the length of the ramp time for each segment.
Each segment can use a unique ramp time.
Effect on Other
Parameters:
No effect on other configuration parameters. Does affect the
setpoint used by the controller.
11.4.3.2 Linking a Ramp Period to an Alarm
Parameter Name
: Ramp Event 1, Ramp Event 2 etc. through Ramp Event 8
(50 through 57)
Name as Displayed
:
rE1rE1, rE2rE2 through rE8rE8
Used By:
all controllers
When Displayed:
if the recipe option is eight-segment r/s recipe, and at least one
alarm is reserved for recipe events using the AlrAlr (alarm) menu
Choices:
disdis disabled
A1.OnA1.On alarm 1 on if alarm 1 is reserved for recipe use
A1.OFA1.OF alarm 1 off if alarm 1 is reserved for recipe use
A2.OnA2.On alarm 2 on if alarm 2 is reserved for recipe use
A2.OFA2.OF alarm 2 off if alarm 2 is reserved for recipe use
Default:
disabled
Description:
Used to link the chosen alarm action with the start of the ramp
time with the same segment number.