Installation manual
Series C Controller Configuration and Operation Manual
11-10 Athena Controls, Inc. 900M050U00
11.4.2.3 Specifying the Number of Additional Times the Multi-Step Recipe Will
Repeat Once Started
Parameter Name
: Recipe Recycle Number (82)
Name as Displayed
:
rcY.nrcY.n
Used By:
all controllers
When Displayed:
if the recipe option is eight-segment r/s recipe
Range:
0 to 99
contcont continuous (once the recipe has been started by an
operator; recipe execution does not start automatically
at power up)
Default:
0
Description:
Used to specify the number of additional times the recipe will be
executed once started. If set to zero, the recipe will execute
once each time the operator starts it. If set to 1, the recipe will
execute twice. If set to 2, the recipe will execute three times,
etc.
11.4.2.4 Specifying What Will Happen to the Multi-Step Recipe After a Power Failure
Parameter Name:
Resume from Power Failure (85)
Name as Displayed
:
Pf.rEPf.rE
Used By:
all controllers
When Displayed:
if the recipe option is eight-segment r/s recipe
Choices:
OffOff off
OnOn on
Default:
off
Description:
Used to indicate whether the recipe execution should resume
after a power failure. If this parameter is set to ONON, then when
power is restored, execution of the recipe will resume at the
point reached before the power failure. If this parameter is set to
OFFOFF, execution of the recipe will not be resumed when power is
restored. If the operator subsequently runs the recipe, execution
will start with segment 1.