Installation manual

Ramp/Soak Recipe Parameters
900M050U00 Athena Controls, Inc. 11-7
11.4 Configuring Multi-Step Ramp/Soak Parameters
11.4.1 Introduction
When the eight-segment ramp/soak recipe option has been selected, several parameters
can be configured that apply to the entire recipe. These include:
recipe holdback that prevents the setpoint from getting too far ahead of the process
value
termination state that determines what happens when execution of the recipe has
been completed
recipe recycle number used to specify the number of additional times the recipe
should be executed once started; this can also be use to set the recipe for
continuous execution
resume from power failure parameter which controls whether execution of a recipe is
resumed after a power failure
After these parameters that apply to the entire recipe have been configured, you
configure up to eight individual segments.
36
Each consists of a ramp time, a soak level
(setpoint) and a soak time. In addition, if at least one alarm has been reserved for recipe
event annunciation, you can specify that an available alarm will go on or off when a ramp
time or soak time starts.
The following diagram shows the first few segments of a recipe and the configuration
used to implement the segments.
36
To configure fewer than eight segments, leave the values of all parameters associated with the un-
needed segments set to OFF or zero.