Installation manual
Series C Controller Configuration and Operation Manual
11-6 Athena Controls, Inc. 900M050U00
11.3.3 Specifying What Happens at the Conclusion of the Single-Setpoint
Ramp Time
Parameter Name
: Termination State (84)
Name as Displayed:
tEr.StEr.S
Used By:
all controllers
When Displayed:
always
Choices:
dEFtdEFt normal mode using default setpoint (setpoint displayed
on front panel)
LAStLASt normal mode using last setpoint reached (same as
default for single-setpoint ramp option)
StbYStbY put controller in standby mode
Default:
put controller in standby mode
Description:
Used to specify what happens at the conclusion of the ramp
time.
Effect on Other
Parameters:
No effect on other configuration parameters. Does affect
setpoint and controller mode of operation. Applied only if the
ramp is allowed to run to completion. If the operator terminates
the ramp up to setpoint by changing the controller mode, the
setpoint used will be the setpoint in effect when the operator
changed the mode.
If you are using the single-setpoint ramp option, you are finished
configuring the recipe parameters. The remainder of this section
does not apply to the single-setpoint ramp option.
Go to Section 12 – Supervisor Parameters.