11. Ramp/Soak Recipe Parameters –
Optional
11.1 Introduction
The 1ZC, 16C, 18C, and 25C can all be configured to execute ramp/soak recipes on
demand. A recipe consists of up to eight segments. For each segment you can
configure a unique ramp time, soak level (setpoint), and soak time. As the controller
executes a segment, the controller gradually (over the period of the ramp time) changes
the currently used setpoint up or down until the setpoint reaches the soak level. During
the duration of the soak time, the controller maintains the setpoint at the specified soak
level. When the soak time has elapsed, the controller executes the next segment of the
recipe.
If at least one front panel alarm was configured for “events”, then you can activate and
deactivate an alarm based on the recipe reaching particular events in its execution, such
as the start of a numbered soak period.
If your process is not responsive enough to achieve the setpoint within the ramp time (or
maintain the soak level for the entire soak time), you can use the recipe “holdback”
parameter to “stop the clock” on the ramp time (and soak time) if the setpoint differs too
much from the process value.
Execution of a recipe can be started, paused, resumed, and terminated using the front
panel (or an optional contact/digital input) on the 16C, 18C, and 25C, or on any of the
controllers (including the 1ZC) using the optional serial communications interface.
Alternatively, all these controllers can be configured to execute a single gradual ramp to
setpoint at startup or on demand.
If both outputs are configured for use with alarms or turned off (using the output type
parameters), then the ramp/soak menu will not be displayed. However, if at least one
output is available for control, then the r-Sr-S (ramp/soak) menu will be available if the
security access level is set to USErUSEr, (user), CnF9CnF9 (configuration) or FACtFACt (factory).
34
34
The access level in all new 16C, 18C, and 25C controllers is set to CnF9CnF9 at the factory. If you cannot
see the ramp/soak menu, the access level has been changed to a more restrictive level. Instructions for
changing the access level are in Section 17.