8.3.5 Integral Action (Automatic Reset) Calculated Automatically During
Autotune for PID Control
This parameter is not used in manual tuning. If you assign a non-zero value to the
manual offset OFFSOFFS parameter, then this parameter IntInt will not be displayed.
Parameter Name
: Integral Action (Automatic Reset) (32)
Name as Displayed
:
IntInt
Used By:
all controllers
When Displayed:
if output 1 or output 2 type is PID
Range:
0.0 to 0.9, 1 to 9600 seconds (See Notes 1 and 2 below.)
Default:
0.0
Description:
Used by the Autotune operation to store the automatic reset
value.
Note 1: The range is reduced when a linear input is used and the value of the dSPLdSPL
(display) menu dEC.PdEC.P (decimal position) parameter is not 0 (zero). See 4.3.2 for more
information about the effect of a linear input on numerical ranges.
Note 2: This parameter is a special case. Even if the value of the dSPLdSPL (display) menu
dEC.PdEC.P (decimal position) parameter is 2 or 3 (which is permitted when a linear input is
used), the maximum number of decimal places applied to the integral offset (automatic
reset) action is 1 (the tenths position).