Installation manual
Series C Controller Configuration and Operation Manual
8-4 Athena Controls, Inc. 900M050U00
8.2.3 Applying Hysteresis to On/Off Control
Parameter Name
:
Hysteresis for Output 1
(21) and
Hysteresis for Output 2
(38)
Name as Displayed
:
HYS.1HYS.1 and HYS.2HYS.2
Used By:
all controllers
When Displayed:
if input type is on/off
Range:
RTD and thermocouple input types: 0 to positive sensor span
linear input types: limited by the scaling defined for the input
using the input menu (See Note 1 below.)
Default:
1
Description:
The hysteresis value represents a temperature value that the
controller uses to move the “on” and “off” transitions away from
the setpoint by an amount equal to half the configured hysteresis
value.
Note 1: The range is reduced when a linear input is used and the value of the dSPLdSPL
(display) menu dEC.PdEC.P (decimal position) parameter is not 0 (zero). See 4.3.2 for more
information about the effect of a linear input on numerical ranges.
If you are configuring control parameters for an on/off output, you
are finished configuring the control parameters that apply to that
output. The remainder of this section does not apply to on/off
outputs.
If both outputs will be used for control, but control parameters for
only one output have been configured, configure the control
parameters for the second output.
• If you chose on/off for the second output, configure the
deadband and hysteresis for the second output as
described here in 8.2.
• If you chose PID control for the other output, go to 8.3.