Specifications

pressed the INDEX key, the unit
will
advance to the High and Low
Calibration
positions.
but index no further until the SETPOINT
key is
depressed.
CAUTION: DO NOT CHANGE THE
CALIBRATION
LOW
[cL(Zero)]
OR
CALlBRATlON
HIGH
[cH(Span)]
ADJUSTMENT
UNLESS YOU INTEND TO, ARE QUALIFIED AND HAVE
A
CALIBRATION
TEST SETUP CONNECTED.
9.
Press Index and Alarm One (Al) appears in the upper display area. If
this option is installed. set in the desired temperature value, then
press ENTER.
10.
Repeat
for
(-A2-)
Alarm two, if installed
11.
Refer to the
section
on tuning the 6075 for the remainder of the
settings.
NOTE: When finished entering all parameters return to
-cd-
using the
INDEX key. Select the level of security desired and enter the appropriate
value into memory.
#1
-
Allows changes to set point
only.
#8
-
Allows changes to first nine parameters
only.
#14
-
Allows changes to 9 parameters and calibration constants.
NOTE: Any other value only allows changes to
-cd-
Reference Notes
NOTE 1: Parameters
#
10 thru
#
16 are accessed from the front panel only,
and can not be set from a remote terminal
NOTE 2: The gain value
(-HG-&-CG-)
is multiplier used to increase the
sen-
sitivity of the controller according
to the
formula: Output
=
Gain (E
+
I
+
D)
where E
=
Error. I
=
Integral. D= Derivative, Its relationship to proportional
band is as follows:
Unit
Span
PROP BAND =
=
Heat Gain (HG) or Cool
Gain
(CG)
Note that proportional band is an inverse function of gain, The range of
18
adjustment is 0 to 400 for Heat. 0 to
400
for Cool.