Specifications
SECTION 5 OPERATION
5.1
Front Panel Features
Touch Key and Indication Operation Layout
1.
2.
3.
4.
5.
6.
7.
Process Temperature or Parameter code is viewed on the upper
display.
Set Point or Parameter setting is viewed on the lower display. Degrees F
and C is also displayed.
Set Point
Key:
Allows user to return to set point
ENTER/TUNE
Key:
Enters a selected value into nonvolatile memory.
Also initiates Auto-Tuning when used in the correct sequence.
Up and Down Keys: Raises and lowers setting respectively. 2 Step scan
rate: Slow and Faster (after 5 seconds).
Index
Key:
Selects Parameters to be addressed
STAND-BY/CANCEL
Key:
Disables outputs. Unit is put in idle mode.
LED above
switch
lights in STAND-BY mode. STAND-BY is also used
as the position from which AUTO-TUNE is accessed. If the key is
pressed during Auto-Tuning the unit will cancel the
Auto-Tuning
pro-
cedure and return to the STAND-BY
mode.
8.
Receive (RX) and
transmit
(TX) lights: Indicate a signal is present at the
communication
port
tights only
momentarily
9.
Heat (HT) a
nd
CooI
(CT) Output
Lighk
Lights when output drive signal
is present
10.
Alarm Lights (A1 and A2): Lights when unit is in alarm. (programmable
Hi, Low, process or deviation.)
12