Specifications

SECTION 3 OUTPUT MODULES
3.1
Module
Description
The Athena 6075 offers field interchangeable output modules. This unique
feature makes it possible to fill output requirements for a variety of
applications with a single controller model.
Module Type B: This
7A/5A
relay (at
120/240
Vac)
is used for driving
resis-
tive
heaters.
NOTE:
Do not use this output module with mechanical
contactors
because they generate an excessive
EMI
field which can interfere
with the
6075’s
microprocessor, Instead, we recommend
“T’
output modules for this application
Module Type
F:
This 4-20mA
output module can deliver full output to loads
having an input impedance of 500 Ohms or less. The cycle time setting
must be ZERO for smooth current output.
Module Type S: Similar to
F.
but pulsed 20 Vdc output
for
driving solid state
relays.
Up
to 6 (input series connected) solid state relays can be used.
Cycle
time can be set to optimize the load response time
requirements.
“F’
&
“S”
MODULE
NOTE:
A
push-on
terminal is
utilized
as a return for ground
currents
of
the
milliamp
source.
It
is connected internally by the mating lug
on the circuit board. To avoid ground loops, drive floating
(ungrounded) loads.
Module Type T:
This solid state relay is capable of 1
amp at
120/240 Vac.
It is
zero voltage switched and
optically
isolated from the drive signal. With it
resistive loads up to
I20
watts at
I20
Vac
and 240 watts at 240
Vac
may
be