Specifications
DIVA8 System VACIE
www.ateis-europe.com
Page 8 of 30
Optional PSSG2, PSS-Touch-G2 or CD8, CD16 remote security paging consoles with higher
or lower priority can be connected for emergency paging purpose outside of the DIVA8
System VACIE rack. These optional devices are powered directly from the DIVA8 System
VACIE rack.
Typical system configuration product requirements:
1x
VACIE Equipment rack, 24U with forced ventialtion
1x
DIVA8MG2, Master unit
1x
DIVA8S, Slave unit
2x
DPAfour250 or SPA2.240, Power amplifier
1x
BECS 150 or equivalent EN54-4 Battery charger
2x
PowerSonic, PS-12750 12V75AH battery or equivalent
Optional:
1x
PSSG2, Security remote desktop paging console
1x
PSS-Touch-G2, Security remote wall- mounted programmable Colour
touch screen remote.
1x
CD8, Security 8-zone remote wall mount paging console
1x
CD16, Security 16-zone remote wall mount paging console
Please&refer&to&7.4&Appendix&A4&Typical&DIVA8&System&VACIE&configuration))
2.1.3. Maximum DIVA8 System VACIE configuration
A maximum system configuration will contain ONE DIVA8MG2 Master unit and FIFTEEN
DIVA8S Slave units, servicing 128 Emergency zones. Emergency Zones following the BS5839
for A/B wiring requires a single loudspeaker cable for zone A or two loudspeaker cables in
case of A and B zoning. The maximum DIVA System VACIE should require a minimum of
TWO amplifiers of type DPAfour250 or SPA2.240 up to a maximum of 16. ONE for every
DIVA8MG2 or DIVA8S Slave unit, generating a total power distribution of 8KW over 128 zones
A/B. All assigned to service the speaker configuration required in the emergency zones.
These devices are to be powered by certified battery-backed power supply, BECS150,
equipped with at least 150AH/24VDC battery pack per 6 amplifiers of type DPAfour250.
The DIVA8 System VACIE should be housed in an IP30 type of cabinet (according to EN 54-
2). This could be TWO Rittal DK type of 40U cabinet or equivalent with forced ventilation.
The VACIE can be supported throughout a network infrastructure including Ethernet Switches
for non emergency remote service applications.
Optional PSSG2, PSS-Touch-G2 or CD8, CD16 remote security paging consoles with higher
or lower priority can be connected for emergency paging purpose outside of the DIVA8
System VACIE rack. These optional devices are powered directly from the DIVA8 System
VACIE rack.
Maximum system configuration product requirements:
2x
VACIE Equipment rack, 40U with forced ventilator
1x
DIVA8MG2, Master unit
15x
DIVA8S, Slave unit
17x
DPAfour250 or SPA2.240, Power amplifier
3x
BECS 150 or equivalent EN54-4 Battery charger
12x
PowerSonic, PS-12750 12V75AH battery