Specifications

DIVA8 System VACIE
www.ateis-europe.com
Page 26 of 30
8.3.2. Battery cascading instruction
Total battery voltage to be connected to the EN54-4 battery charger and monitoring unit
should be 24VDC ( 19VDC 26.5VDC). To achieve this, two Power sonic PG-12V75 batteries
can be connected in series as shown in figure 7. (Total capacity: 75AH - 1800WH)
Important: Red and blue wires should be equal in size and length.
Figure 7: 24VDC/75AH arrangement
Higher capacity can be obtained by applying a series-parallel circuit as shown in figure 8.
(Total capacity: 150AH - 3600WH)
Important: BLACK and GREEN wires should be equal in size and length.
RED and BLUE wires should be equal in size and length.
Figure 8: 24VDC/150AH arrangement