User Manual

Three Different Controllers Offer Programmability Choices
1
Specification Programmable -P Programmable -PT Manual -M
Controller Type Programmable controller Fast Transient controller Manual control oscillator
Voltage
Range 0 - 135 V / 0 - 270 V L-N 0 - 135 V / 0 - 270 V L-N Variable pot control
Programmable range change Programmable range change Switchable range change
Individual phase programming Individual phase programming Option -RPV for 0-FS control
using 0 - 10 VDC input.
Accuracy ± 0.135V from 5 V to 135 V ± 0.7 % FS from 5 % to FS Variable control
± 0.54 V from 135 V to 270 V Constant line, load and Analog meter readback
@ 25° C ± 1° C temperature @ 25° C ± 1° C
Load Regulation TRMS Sense: ± 0.05 % FS - 0.5 % FS from 45 Hz to 100 Hz ± 0.05 % from 45 Hz to 5 kHz
no load to full load - 2 % FS from 100 Hz to 550 Hz
Line Regulation ± 0.02 % FS for ± 10 % ± 2 % of full output for ± 0.02 % of full output for
line change a ± 10 % line change a ± 10 % line change
Stability ± 0.015 % FS over 24 hours at ± 0.25 % FS over 24 hours at ± 0.015 % FS over 24 hours at
constant line, load and temperature constant line, load and temperature constant line, load and temperature
Initial value 0.0 or 5.0 Vrms field selectable 0 Vrms N/A
Settling time 16 msec, no-load from 0.5 msec N/A
5 V to within 2 % of final value;
16 msec, full load from
5 V to within 15 % of final value
Programmable THD N/A 0 - 20 % THD clipped sine N/A
1 % resolution
Amplitude Modulation N/A 0 to 5 V RMS generates 0 to 11 % 0 to 5 V RMS generates 0 to 11 %
amplitude modulation of output amplitude modulation of output
voltage. 45 Hz to 5 kHz input voltage.
Frequency
Range 2750L-1P, 4500L-1P 6000L, 12000L and 18000L: 2750L-1M, 4500L-1M
and all multibox systems: 45 to 440 Hz and all multibox systems:
45 Hz to 2 kHz All other models: 45 Hz to 2 kHz
-3P and 751L - 2001L: 45 Hz to 550 Hz -3M and 751L - 2001L:
45 Hz to 5 kHz 45 Hz to 5 kHz
6000L, 12000L and 18000L: 6000L, 12000L and 18000L:
45 Hz to 440 Hz 45 Hz to 440 Hz
Resolution 0.01 Hz; 45.00 Hz to 99.99 Hz 0.01 Hz; 45.00 Hz to 99.99 Hz 3 digits
0.1 Hz; 100.0 Hz to 999.9 Hz 0.1 Hz; 100.0 Hz to 550.0 Hz
1 Hz; 1000 Hz to 5000 Hz
Accuracy ± 0.001 % of programmed value ± 0.001 % of programmed value ± 0.005 % of set value
Initial value Any within range Any within range Setting
External Sync Input TTL level TTL level N/A
Phase
Range Phase B and/or C relative to Phase B and/or C relative to N/A
phase A: 0 to ± 360° in 0.1° phase A: 0 to ± 360° in 0.1°
increments increments
Accuracy ± 2 ° ± 2 ° ± 3 °
Current
Programmable Limit Adjustable trip Adjustable trip Adjustable foldback with
recovery
Remote Inhibit Contact closure turns Contact closure trips unit Contact closure turns
output off off. Sets defaults. output off
Measurements
Voltage resolution 0.1 Volt, accuracy ± 10 digits N/A
Current resolution 0.01 Amp or 0.1 Amp, accuracy ± 10 digits N/A
Power resolution 1 W or 0.01 kW, accuracy ± 10 digits N/A
Phase angle resolution 0.1°, accuracy ± 2° to 2 kHz, ± 3° to 5 kHz N/A
Power Factor range 0.000 to 0.001 N/A
Frequency resolution four decades, accuracy ± 0,02 Hz to 99.99 Hz, N/A
± 0.2 Hz to 500.0 Hz, ± 0.5 Hz to 999.9 Hz, ± 10 Hz to 5 kHz
Apparent Power resolution 1 VA or 0.01 kVA, accuracy ± 10 digits N/A
Note 1 One of these three controller types must be specified when ordering a L Series power source or, for Arbitrary waveform generation,
refer to the HGA controller.