Instruction Manual
40
Supplemental Characteristics
for all model numbers
dc Floating Voltage: Output terminals
can be floated up to ±240 Vdc from
chassis ground
Output Common-Mode Noise Current:
(to signal ground binding post)
500 µA rms, 4 mA peak-to-peak
Remote Sensing: Up to half the rated
output voltage can be dropped in each
load lead. The drop in the load leads
subtracts from the voltage available for
the load.
Command Processing Time: Average time
required for the output voltage to begin
to change following receipt of digital
data is 20 ms for the power supplies
connected directly to the GPIB.
Modulation: (Analog programming of
output voltage and current)
Input Signal: 0 to –4 V for voltage,
0 to 7 V for current
Input Impedance: 60 k Ohm or greater
Input Power: 3,800 VA, 2,600 W at full
load; 170 W at no load
GPIB Interface Capabilities: SH1, AH1, T6,
L4, SR1, RL1, PP0, DC1, DT1, E1, and C0.
IEEE-488.2 and SCPI-compatible
command set
Regulatory Compliance: Listed to UL1244;
certified to CSA556B; conforms to
IEC 61010-1.
Size:
425.5 mm W x 132.6 mm H x 640 mm D
(16.75 in x 5.22 in x 25.2 in)
See page 102 for more details
Weight: Net, 28.2 kg (62 lbs);
shipping, 31.8 kg (70 lbs)
Warranty Period: Three years
Single-Output: 2000 W GPIB (Continued)
Specifications
(at 0
˚
to 55
˚
C unless
otherwise specified)
6671A- 6671A- 6671A- 6672A- 6673A-
J03 J04 J17 J04 J03
Special Order Special Order Special Order Special Order Special Order
Option Option Option Option Option
Number of outputs 11111
GPIB Yes Yes Yes Ye s Yes
Output ratings
Output voltage 14 V 10 V 15 V 24 V 37.5 V
Output current 150 A 200 A 120 A 85 A 45 A
Programming accuracy
at 25
˚
C ±5
˚
C
Voltage 0.04%+ 14 mV 10 mV 15 mV 25 mV 37.5 mV
Current 0.1%+ 90 mA 125 mA 90 mA 60 mA 40 mA
Ripple and noise
from 20 Hz to 20 MHz
Voltage rms 1.5 mV 750 µV 1.5 mV 1 mV 800 µV
Voltage peak to peak 15 mV 9 mV 15 mV 11 mV 9 mV
Current rms 150 mA 200 mA 150 mA 100 mA 40 mA
Readback accuracy at 25˚C ±5˚C
(percent of reading plus fixed)
System models only
Voltage 0.05% + 25 mV 15 mV 27 mV 40 mV 53.5 mV
±Current 0.1% + 110 mA 150 mA 110 mA 100 mA 60 mA
Load regulation
Voltage 0.002%+ 600 µV 300 µV 650 µV 650 µV 1.2 mV
Line regulation
Current 0.005%+ 7 mA 10 mA 7 mA 7 mA 4 mA
Transient response time Less than 900 µs for the output voltage to recover 100 mV following a
change in load from 100% to 50% or 50% to 100% of the output current
rating of the supply
Supplemental Characteristics (Non-warranted characteristics determined by design and
useful in applying the product)
Average resolution
Voltage 4 mV 2.5 mV 4 mV 6 mV 10 mV
Current 40 mA 55 mA 35 mA 22 mA 15 mA
OVP 28 mV 20 mV 30 mV 42 mV 65 mV
Output Voltage programming
response time*
(excluding command 30 ms 35 ms 35 ms 70 ms 130 ms
programming processing time)
*Full load programming rise/fall time (10% to 90% or 90% to 10%) with full resistive load equal to rated output
voltage/rated output current.
Power Products Catalog 2002-2003
For more detailed specifications see the product manual at
www.agilent.com/find/power
Agilent Performance dc Power Supplies speed and accuracy for test optimization