Cut Sheet

NOTE: For 3-Phase Wye applications, it is normal for the “GND”
indicators not to flash unless a phase is lost.
\\\
ORDERING INFORMATION
MODEL NUMBER
DESCRIPTION
UPA-130 30mm Universal Power Alert
Accessories
UPA-WP40 ANSI Warning Plate
UPA-BZL
Flush Mounting Kit for 1-1/4”
Conduit Knockout
DETECTOR INCLUDED FAULT CURRENT (PHASE-TO-GROUND SHORT)
3- Phase Line-To-Line (VAC) 30 120 240 480 750
0 OHM Phase-To-Ground Current (µ
A)
28 108 219 455 730
GND DETECTOR THRESHOLDS (LEAKAGE ANY PHASE-TO-GROUND)
3- Phase Line-To-Line (VAC) 30 120 240 480 750
L1, L2, or L3 To Ground Continuity (OHMS)
2M 2M 3M 5M 7M
Detector Included Fault Current (µ
A)
7 26 38 60 67
INDICATOR FLASH RATES (L1, L2, L3, GND)
3- Phase Line-To-Line (VAC) <29 30 120 240 480 600 750
Flashes/Sec (Typical) 0 1.3 4.2 5.8 7.3 8.0 8.8
DC or Stored Energy (VDC) <27 30 48 110 300 600 1000
Flashes/Sec (Typical) 0 1.6 2.5 4.5 6.9 8.8 9.1
\\\
SPECIFICATIONS
OPERATIONAL RANGE
AC SINGLE OR 3-PHASE
40 to 750 VAC, 50/60/400 Hz, (LINE-TO-LINE or LINE-TO-GND
(UL Approved 50/60 Hz))
DC OR STORED ENERGY 30 to 1000 VDC, (LINE-TO-LINE or LINE-TO-GND)
MAXIMUM RATED
VOLTAGE
750 VAC/1000 VDC (LINE-TO-LINE or LINE-TO-GND)
DETECTION THRESHOLDS
29 VAC 3-Phase, 40 VAC SINGLE-Phase, 27 VDC (TYP CUTOFF)
POWER CONSUMPTION
1.2 Watts @ 750 VAC (Approximately)
TEMPERATURE RATING
Operate -4° to 131°F (-20° to +55°C)
Storage -40° to 185°F (-40° to +85°C)
ENCLOSURE
Totally Encapsulated for Environment Protection
TERMINATIONS
(4) 6ft, 18 AWG 1000V,
UL-1452
RED YEL BLU GRN
A Ø B Ø C Ø GRD
WEIGHT
7 oz.
UPA-130 Series
Diversified Electronics atcdiversified.com 800.727.5646
280
Power Alerts
// UPA-130 Series
Verification of Stored Energy Inside A Panel
Fits 30mm Knockout
Redundant Circuitry
40-750 VAC, 30-1000 VDC
The UPA 130 Power Alert
reduces the risk of electrical arc flash by
pre-verifying the electrical isolation from outside of a control panel.
H
ardwired to the circuit breaker or main disconnect, the UPA flashes
whenever voltage is present. Engineered with redundant circuitry, the
Power Alert is powered by the same volatage that it indicates.
The eight detector UPA-130 visually alerts to the presence of dangerous AC
or DC (Store Energy) potentials occurring between any combination of the
four monitored input lines (L1, L2, L3, GND). Two LED indicators are assigned
to each input line and are designated "+" and "-". For each input line carrying
an
AC potential (bi-polar) , both the "+" and "-" LEDs will be active. A DC or
Stored Energy potential
will illuminate the "+" LED for the positive line and the
"-" LED for the negative line.
3
0
m
m
U
n
i
v
e
r
s
a
l
P
o
w
e
r
A
l
e
r
t
NEMA 4X
\\\
OPERATION

Summary of content (2 pages)