User`s manual
614 Automatic Swinger Bypass
#
615 Permanent Bypass?
#
616 Bypass Group Description
1
6chrs
================700
Series: System Outputs
710 Series: Gerieral
711 Fire Cadence Option
#
0= Intermittent cadence; 1= Continuous cadence. If 0, fire
cadence will be about 2 second ON and 1 second OFF. “lntru-
sion,” “Police,” and “Panic” will take whichever cadence “fire”
does not take.
712 Chime Option
#
=
Don’t allow; 1= Do allow chime. If
“1”
and a sensor/zone is
set to chime for a Level of Protection (see Fn#s 41
l-414),
then
keypads will chime if the sensor is violated and the system is in
that Level of Protection. User can change this function through
user programming.
NOTE: A user control and a dip-switch on each keypad allow
silencing the Tone and Chime for that keypad.
720 Series: Sirens
CATEGORIES
1= Entry/Exit
2=
Perimeter
3=
Interior
4=
24_Hour/Perimeter
Tamper
721 Siren/Bell
#1
Cadence
5= Interior Tamper
9= Silent Panic
13=
Trouble Category
6= Day Zone 10= Fire
14=
Auxiliary(
1)
7= Non-Alarm 11= Emergency
15=
Auxiliary(2)
8= Audible Panic
12=
Environmental
16=
Keyswitch
#
=
termittent cadence; 1= Continuous cadence. This selec-
tion determines if the power output from the CCU to siren
#1
will
be constantly on, or controlled by
Fn#711.
0 yields control to
Fn#711,
1 overrides
Fn#711.
0= Don’t Auto-bypass a Swinaer;
1-8=
Yes, do. The number
entered indicates the number of violations allowed before the
sensor is Auto-bypassed. The bypass remains in effect until the
system Level of Protection is changed. (Entering “1” means that
the first violation will be processed as an alarm, but the second
will not and the sensor will be bypassed.)
NOTE: Priority sensors will also be Auto-bypassed;
Fn#611
overrides this function.
0=
Don’t allow permanent bypass; = 1 = Do allow. If 0, then each
bypass
must be re-entered each time before the user can arm a
system. (See also
Fn#611)
If bypass reporting is enabled,
permanent bypasses are only reported when created, and
again when removed.
Describe bypass group (see Fig 3-l for reminder on entering
characters).
Fn#520
allows assigning sensors to a group that
can all be bypassed with a single bypass command. An
example would be bypassing the pool, back door, and Family
Room/bar area while protecting the rest of a household; or
bypassing a loading dock and store-room while protecting other
loading docks and the rest of a business. Default
=
BYPASSGROUP (zone 999)
(-
3-203-20
AT&T Security System 8300 Installer’s Manual