Instruction manual

ENVIRONMENTAL REQUIREMENTS
AC Power Requirements
Each System 25 cabinet requires 500 Watts at 115V ac (maximum).
The System 25 power service must be a dedicated branch circuit with no other equipment
served (see Figure 6-3). The customer should provide a load center of appropriate current
rating (ITE EQ4 typical) equipped with 120V ac, 15 ampere (AMP), single pole magnetic
circuit breaker(s) (ITE QP1-BO15 typical).
Each breaker is to protect 2 associated wall
mounted 115 V ac, 15 AMP, receptacles (HUBBELL 5262 typical). Grounding of this load
center is to be provided by a “Green Wire” ground extended from the grounding electrode
conductor at the AC service entrance to the load center.
The following materials are required:
Single Cabinet System
1 - 15 AMP 3 Wire Dedicated Branch Service
1 - 4" Box (RACO 230 or Equiv.)
1 - 4" Cover (RACO 807 or Equiv.)
1 - Ground Bar (Square D PK9GTA or Equiv.)
2 - Recpt. (Hubbell 5262 15 AMP or Equiv.)
Multiple Cabinet System
2 - 15 AMP 3 Wire Dedicated Branch Service
2 - 4" Box (RACO 230 or Equiv.)
2 - 4" Cover (RACO 807 or Equiv.)
1 - Ground Bar (Square D PK9GTA or Equiv.)
4 - Recpt. (Hubbell 5262 15 AMP or Equiv.)
Typically, multiple cabinet systems can be powered from a single phase 120V ac, 60 Hertz
service (two 15-amp circuits required). There are no phase restrictions between cabinets.
Therefore, the two 15-amp circuits required may be
service.
The receptacles should be located at least 1 foot above
located further than 4 feet from the cabinets.
DANGER
derived from single or three-phase
the floor. Receptacles should not be
Under no circumstances should this equipment
be connected to 220V ac; doing so poses a
serious fire hazard.
6-8