Installation guide

Zone Grouping
This option allows you to select a group of zones to be paged at the same
time, The number of zone groups that can be formulated is eight; the
maximum number of zones per group is 56 zones.
The factory default is NONE (there are no default zone groups).
Programming Steps
First access the PagePac Plus system and enter the programming mode
by pressing [
* ] [ * ] and entering your Programming password (if optioned).
You may exit the programming mode by dialing [
# ].
You will need to repeat this procedure for each zone group you wish to
set up.
1.
2.
3.
Dial [
6
] [
4
] to select this option.
Hear a DOUBLE beep.
Enter the zone code, of the zone group to be defined. For example,
[
8 ] [ 0 ] for group 80. Use ALIAS numbers, if optioned. Otherwise
use Physical zone/group numbers.
Hear a DOUBLE beep.
Enter zone codes of zones to be included in the group. A # will
terminate the string. For example, [
0 ] [ 1 ] [ (tone) ], [ 0 ] [ 2 ] [ (tone) ],
[
1
] [
3
] [
(tone)
], [
1
] [
4
] [
(tone)
], [
#
] indicates zones 1, 2, 13, and 14 are
included in this group. Enter the codes consecutively, with no digit or
character between them. Use ALlAS numbers, if optioned.
Othervise, use Physical zone/group numbers.
After entering a valid zone code, you will hear a confirmation tone,
then a dial tone, and then you enter the next valid zone code or [
# ]
to end the string.
Hear TRIPLE beeps.
To verify the zone group assignment, dial [
6 ] [ 5 ] and repeat steps 2 and 3
above.
These actions are summarized in table 2-15.
Table 2-15. Zone Grouping
Feature
Mode Option/
Verify
Dial
Listen
For
Zone/Group
Selection
Listen
For
Choose Option
Listen
For
Default
Zone
Grouping
To Select
To Verify
64
65
Double
Beep
Enter
group
number.
Double
Beep
Enter zone
numbers. A # will
terminate the string.
Triple
Beeps
NONE
2-22 Programming The Controller