AC Power and Grounding
2-7
Installing the Control Unit
All AC outlets must connect to the same load center and the ground wire
must connect to the single-point ground bar on the first AC outlet (see
Figure 2-1).
One outlet must have an attached ground bar connected by a #6 AWG
copper wire to an approved ground (see Approved Grounds later in this
chapter, for a description of approved grounds). This ground bar is the
systems single-point ground (see Figure 2-1).
To prevent someone from accidentally shutting off the power, do not
connect the control unit to a switch-controlled outlet.
The AC outlet should be within 5 feet (152 cm) of the control unit.
Each carrier requires one AC outlet receptacle.
Auxiliary equipment requires additional AC outlets.
If a printer or PC is installed on the system, it must be plugged into the
same AC branch as the power supply of the basic carrier.
If the printer or PC is 50 feet (15 m) or more from the control unit, or is
plugged into a different AC circuit, Asynchronous Data Units (ADUs) must
be installed as well. Chapter 5, Installing the PC, CAT, or Printer of the
Installation manual includes complete installation instructions.
The AC power requirements indicated in AC Outlet Tests, must be met.