Instruction manual
The Control Unit
1-2
Installation, SPM, Maintenance, and Troubleshooting Supplement
Power Supply 1
CAUTION:
Grounding circuit continuity is vital for safe operation of the MERLIN 
MAGIX system. Never operate with the grounding conductor 
disconnected. The ground-screw connection is located on the carrier.
The 491D1 (100–240 V AC) power supply modules can provide up to 96 unit 
loads of current per carrier; therefore, an auxiliary power unit is not required 
with these modules. In addition, three test points are provided for measuring 
DC voltage outputs.
Power Specifications 1
Each 491D1 power supply draws a maximum current of 5.4 amperes at 117 V 
AC (60 Hz); the 491D1 power supply draws a maximum current of 3.1 amperes 
at 220 V AC (50 Hz). Output power is:
+5.1 V DC (10A), –5.1 V DC (1.5A), –48 V DC (3.0A)
Test Points  1
There are three voltage test points, one each for the +5.1 V DC, –5.1 V DC, and 
–48 V DC outputs. These test points enable service personnel to measure the 
+5.1 (± 5%), –5.1 (± 5%), and –48 V DC (± 10%) outputs delivered to the 
MERLIN MAGIX backplane. Use the ground terminal when measuring the 
output voltages at these test points.
Outside the North American continent, the power cord plug on the 
491D1 power supply module may need to be replaced with an IEC 
(International Electrotechnical Commission) approved plug (at 
least 10 amps and 250 volts).