Specifications

Power Supply Unit Load Requirements
(continued)
Unit Load Calculation Rules
(continued)
Installed
Mode
Modules
Calculation
Square
5 or more
Use the “Unit Load Rating of
Key/
System Modules” table and
Behind
instructions below to determine
Switch
the estimated ULs:
If ULs equal 54 or less, an
Auxiliary Power Unit 9024 is
not required.
If ULs exceed 54, use “Unit
Load Rating of System
Modules” table to determine
the actual ULs for the system.
If the actual ULs exceed 54,
try to exchange modules
between carriers to reduce the
ULs below 54.*
If the modules cannot be
exchanged to reduce the ULs
below 54, an Auxiliary Power
Unit 9024 is required.
*
Empty slots are not permitted between modules.
Page 50