ENVIRONMENTAL REQUIREMENTS
PRINTER (OPTIONAL)MANAGER ITERMINALCHAIRTRUNK/AUXILIARYFIELD (NOTE 7)WALL
NOTES:POWER OUTLETS MUST NOT BE UNDER SWITCH CONTROL, MUST NOT BE SHARED WITH OTHEREQUIPMENT, AND SHOULD BE LOCATED OUTSIDE THE CROSS-CONNECT FIELD AREA.PROCESSOR PORT NETWORK CABINET REQUIRES A SPECIAL 120-VOLT, 60-HZ, 50-AMP POWEROUTLET (NEMA 5-50R RECEPTACLE, OR EQUIVALENT).AUXILIARY CABINET REQUIRES A SPECIAL 120-VOLT, 60-HZ, 20-AMP POWER OUTLET(NEMA 5-20R RECEPTACLE, OR EQUIVALENT).ALLOW AT LEAST 36 INCHES (91.4CM) OF SPACE IN FRONT OF CABINET TO PERMIT DOOR TOSWING OPEN.SYSTEM MUST BE GROUNDED BY ONE OF THE APPROVED METHODS.EARTHQUAKE PROTECTION MAY BE REQUIRED.THE TRUNK/AUXILIARY FIELD MAY BE LOCATED WITHIN THE CROSS-CONNECT FIELD.EACH MCC CABINET USES 10-FOOT B25A CABLES FROM THE D AND E CABINET POSITIONS AND15-FOOT B25A CABLES FROM THE A, B, AND C CABINET POSITIONS. FIBER CONNECTIONSBETWEEN PORT NETWORKS USE 20-FOOT (FL2P-P-20) FIBER CABLE.
NOTES 1 AND 3
1.2.3.4.5.6.7.8.
T ABLENOTES 1 AND 2CABLE SLACKMANAGER(NOTE 8)Z113ACABLE SLACKMANAGER(OPTIONAL)Z113APROCESSORPORTNETWORKCABINET(FRONT)AUXILIARY CABINET(OPTIONAL)NOTES 4,5, AND 632” 32”28”28” 38”CROSS-CONNECT FIELD (EXTEND AS REQUIRED)
FIGURE 11. Typical Multi-Carrier Cabinet Floor Plan
With Processor Port Network and Auxiliary Cabinet
106