Instruction manual
POWER AND GROUNDING
DC Power Requirements
Multicarrier Cabinet System
A DC power plant maybe used to power the multicarrier system cabinets. Figure 31 shows a typ-
ical power and grounding layout for a DC-powered multicarrier cabinet.
EXPANSION PORT
PROCESSOR PORT
NETWORK (EPN) CABINET
NETWORK (PPN) CABINET
FRONT
FRONT
DC POWER
DISTRIBUTION
UNIT
-48V ❍
❍
-48 V RTN
-48 V
-48 V RTN
REAR
DC POWER
DISTRIBUTION
UNIT
REAR
CABINET
GROUND
BLOCK
SYSTEM
SINGLE
POINT
GROUND
❍
❍ ❍
❍ GROUND
(75A (75A
APPROVED
❍ DISCHARGE
GROUND
BAR
❍
(SEE NOTE)
-48 V
10 AWG
COUPLED
BATTERY PLANT
BONDING
CONDUCTOR
CABINET
GROUNO
BLOCK
1-AWG UP
TO 50 FEET
OR ENGINEERED
FOR LESS
THAN 1%
VOLTAGE DROP
(CBC)
NOTE:
USE APPROVED GROUND LOCATED NEAREST THE TELEPHONE
COMPANY OWNED PROTECTOR GROUND BLOCK AT THE
BUILDING ENTRANCE FACILlTY
FIGURE 31. Typical Multicarrier Cabinet System DC Power and Grounding Layout
(EPN Colocated)
166