Instruction manual
ENVIRONMENTAL REQUIREMENTS
WALL
NOTES 1 AND 2
NOTES 1 AND 3
CROSS-CONNECT FIELD (EXTEND AS REQUIRED)
______
TRUNK/AUXILIARY
FIELD (NOTE 7)
38"
TABLE
PRINTER MANAGER I
(OPTIONAL)
TERMINAL
28"
32"
32"
CHAIR
CABLE SLACK CABLE SLACK
MANAGER
MANAGER
(NOTE 8)
(OPTIONAL)
Z113A
Z113A
PROCESSOR AUXILIARY
PORT
CABINET
NETWORK
(OPTIONAL)
28"
CABINET
(FRONT)
NOTES 4,
5, AND 6
NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
POWER OUTLETS MUST NOT BE UNDER SWITCH CONTROL, MUST NOT BE SHARED WITH OTHER
EQUIPMENT, AND SHOULD BE LOCATED OUTSIDE THE CROSS-CONNECT FIELD AREA.
PROCESSOR PORT NETWORK CABINET REQUIRES A SPECIAL 120-VOLT, 60-HZ, 50-AMP POWER
OUTLET (NEMA 5-50R RECEPTACLE, OR EQUIVALENT).
AUXILIARY CABINET REQUIRES A SPECIAL 120-VOLT, 60-HZ, 20-AMP POWER OUTLET
(NEMA 5-20R RECEPTACLE, OR EQUIVALENT).
ALLOW AT LEAST 36 INCHES (91.4CM) OF SPACE IN FRONT OF CABINET TO PERMIT DOOR TO
SWING OPEN.
SYSTEM MUST BE GROUNDED BY ONE OF THE APPROVED METHODS.
EARTHQUAKE PROTECTION MAY BE REQUIRED.
THE TRUNK/AUXILIARY FIELD MAYBE LOCATED WITHIN THE CROSS-CONNECT FIELD.
EACH MCC CABINET USES 10-FOOT B25A CABLES FROM THE D AND E CABINET POSITIONS AND
15-FOOT B25A CABLES FROM THE A, B, AND C CABINET POSITIONS, FIBER CONNECTIONS
BETWEEN PORT NETWORKS USE 20-FOOT (FL2P-P-20) FIBER CABLE.
FIGURE 21. Typical Multicarrier Cabinet Floor Plan
With Processor Port Network and Auxiliary Cabinet
150