Specifications

Electrical
90–130 VAC, 50–60 Hz, 3-prong outlet separate ground, separately fused at 15 Amps
Requirements
On a PARTNER
II
220V System: 180–264 VAC, 50–60 Hz, fused at 10 Amps
Outlet must not be controlled by an on/off switch
Grounding to comply with Underwriters Laboratories (UL) 1459:
A.
B.
C.
An insulated grounding conductor that is not smaller in size and equivalent in insulation
material and thickness to the grounded and ungrounded branch circuit supply conductors,
except that it is green with or without one or more yellow stripes,
is to be installed as part of the
circuit that supplies the product or system.
The grounding conductor mentioned in item A is to be connected to ground at the service
equipment.
The attachment-plug receptacles in the vicinity of the product or system are all to be of a
groundinq type, and the grounding conductors serving these receptacles are to be connected
to earth ground at the service equipment.
Safety
U.S.: Meets UL 1459 Issue 2
Requirements
Canada: Meets CSA C22.2, 225
Government
U.S.:
FCC Part 68
Approvals and
FCC registration number (U.S.): AS5 USA-61630-KF-E
Local Phone
FCC Part 15 Class A
Company
REN (outside line jack): 0.9A per line jack
Information
Jack type: RJ11C
Loop start lines
Canada:
DOC CP01, Issue 7
DOC registration number (Canada): 230 3756A
DOC CS03, Issues 6 & 7
Load Number = 7
Loop start lines
A-2 Specifications