Anti-cold wind when compressor runs:
①When TE is in rise status, if Te<30℃,the indoor fan turns off;30℃≤TE<38℃,the indoor fan runs
at low fan speed;Te≥38℃, the indoor fan runs at setting wind speed;
②When Te in fall status, if TE>34℃,the indoor fan runs at the setting fan speed;28℃<TE≤34℃,the
indoor fan runs at the low fan speed;TE≤28℃,the indoor fan turns off.
(Picture 1)
Anti-cold wind function when compressor stops:
① When TE is in the fall status, if TE>30℃,the indoor fan runs at low fan speed;TE30≤℃,indoor
fan turns off;
② When TE is in the rise status, if TE35≥℃, the indoor fan runs at low fan speed; TE35<℃, indoor
fan turns off;
(Picture 2)
Residual-heat removing function after air-conditioner stops:
When TE>35℃,the indoor fan runs at the low fan speed, if≤35℃,the indoor fan turns off, and
air-conditioner stops for starting the process of residual heat removal and last for ≤10seconds, within