Service manual

AUX air conditioner service manual
31
Chapter 2 Introduction of AUX products
Section one the basic functions introduction of Electric controller
.The characteristics of the appearance and structure
1. The appearance photos of the outdoor unit
outdoor unit 1 outdoor unit 2 outdoor unit 3
2. The appearance photos of the remote controller (applicable for Model 9000BTU~24000BTU )
YK(R)-F/001E( YKR-F/002E ) YK(R)-C/02JE YK(R)-C/01E
. The basic function introduction of the split wall-mounted type Electric-controller
(9000BTU~12000BTU):
1. The basic conditions for the operation of the controller
The applicable voltage range of the electrical powe r: The input voltage 103 V – 130V;
Th e input AC current frequency: 60Hz
The operating temperature for electric controller: -10~+70 ;
The operating moisture for electric controller: RH20%~RH90%;
The indoor fan: RP plastic -sealed motor, three impulse feedback signal;
The outdoor fan: tap iron-shell motor, only one speed range and the normal working current shall be
lower than 1.5A;
The normal working current of t he four-way valve: lower than 1.9A/115VAC;
The Swing Motor: DC12V, Four phase eight step stepping motor;
Compressor: Single -phase power supply, the normal working current shall less than 15A.
2. Functions of the electric controller
The function of the controller consists of the following parts:
The remote control receiving function;
LED/ Digital displaying function;
Force operation function;