AUX air conditioner service manual Foreword In order to guide after services of all installation and maintenance agents, provide all necessary information of AUX air conditioners, and make the whole service network working under the service concepts of AUX Co. Ltd, we prepare this Service manual. This Manual is mainly composed of 6 parts: Part I, i.e.
CONTENTS Chapter 1 The operation theory of the Room Air-Conditioner………………………………………1 Section one- the basic knowledge of pyrology and ventilation…………………………………...1 Section two- the basic knowledge of refrigeration………………………………………………..7 Section three- the basic structure of the air-conditioner…………………………...……………..18 Chapter 2 Introduction of AUX products…………………………………………………………...31 Section one- the basic functions introduction of electric controller………………………….…..
AUX air conditioner service manual Chapter 1 the operation theory of the Room Air-Conditioner Section one the basic knowledge of pyrology and ventilation 1. Basic Definition ⑴ Temperature Temperature is a physical value for the definition of the percentage of the cold and heat to an object. It’s the one of those basic parameters used in confirming the substance’s status.
AUX air conditioner service manual The pressure is distinguished by gauge pressure and absolute pressure applied in the practice. The gauge pressure is validated according to the numerical value shown on the pressure gauge. This value, based on an atmospheric pressure (0), is the difference of the actual pressure of the tested gas and the ambient atmospheric pressure. If the value is lower than the atmospheric pressure, then it will be negative and called vacuum value (B).
AUX air conditioner service manual applied in the separating process by the gas & liquid separator. ⑷Heat Energy The heat energy of the substance, the internal energy, is the sum of the kinetic energy and potential energy. The quantity of heat is the physics parameter for measuring the heat absorbed or released by the physical object, and is one of the representation forms of energy. The essential of the heating process of refrigeration is the process of transmitting heat energy.
AUX air conditioner service manual your hand will feel heated. Different materials have different heat conductivity. In this case, the heat conductivity coefficient was introduced as the unit of the value for measuring purpose. Such coefficient represents the amount of heat that passes by conduction through a one meter thickness of homogeneous material, per one hour and per one square meter Measured as 1℃ difference between the two surfaces of the material. Its unit is kJ/ (m.h.
AUX air conditioner service manual impacted by force, for example the convection of the refrigerant inside the pipes caused by the impact from the compressor of the refrigerator and air-conditioner, and the forced convection to the condenser and evaporator impacted by the fan. The heat transfer coefficient is directly proportional to the flow speed of the forced convection. So, the fan can be utilized as a forced convection tool for creating the effective heat transfer.
AUX air conditioner service manual water in the air within the temperature zone under 100℃, the absolute humidity can be represented by the pressure value created by the water vapor in the air. The pressure unit is: Pa. Less relative humidity means more dry of the air. Zero percent of the relative humidity value means 100 percent dry air. 100 percent of the relative humidity means the saturation humidity of the air. The value of the relative humidity is measurable by the hygrometer.
AUX air conditioner service manual temperature value shall be determined by the industry & mineral enterprises, scientific & research institutes, medical and sanitary units according to their own specific purposes. The process of air temperature conditioning is substantially the process of adding or reducing sensible heat. The value of the air temperature also expresses the quantity of the sensible heat of air.
AUX air conditioner service manual ②Freon species refrigerant They are the ramifications of methane and ethane with the changing character in consequence of the quantities variety of the atoms of fluorine, hydrogen and chlorine.
AUX air conditioner service manual ⑴The requirement for the thermodynamic character The basic requirements the refrigerant shall meet are: ①Under the standard atmosphere pressure, the evaporation temperature must be low and generally shall not higher than -10℃. The pressure value under the normal evaporation temperature shall be higher or closed to the atmosphere pressure value in case of the air’s in leakage to the system.
AUX air conditioner service manual specific type and temperature of the lubricating oil. The capacity per unit of R22 is almost same as the one of R717 while it will be higher than R22 under a low temperature.R22 is usually applied in the middle temperature refrigerating systems with the object lowest refrigerating temperature of up than -60℃. ⑵ The property of the replacement cold medium of R407C, R410a, etc.to R22 The properties comparison between R410A, R407C and HCFC22 is listed in table 2-2.
AUX air conditioner service manual Lubricating oil Slippage temp.℃) Capacity of refrigeration (%) COP(%) Lubricating oil Mutual solubilization 0 <0.17 4~6 100 141 101 100 Mineral oil Good 92.5 POE Fair 97 POE Fair 2. The theory of refrigeration There are many methods in artificial refrigeration. The most popular one among of them applied in practice is the steam-compressing type.
AUX air conditioner service manual high temperature mediums. It’s absolutely necessary to a refrigeration system without lack of the Compressor, Condenser, Throttle device and Evaporator. As to the other auxiliary parts, they are configured and constructed in order to promote the economy, the reliability and the safety of the system.
AUX air conditioner service manual operation under the rating working status and the specified condition. ⑷Heating capacity It means the total quantity of heat per unit time transferred by the air-conditioner to the closed space, room or area under the rating working status and specified condition. Unit: W or BTU. ⑸The consumed power for heating: The total power input for air-conditioner’s heating operation under the rating working status and the specified condition Unit: W.
AUX air conditioner service manual electrical appliances and other factors. Basing on the experience, we can set the value of 150—240W/M2 (120—300W/M2 is applicable in more large room or space) as the cooling load per unit working area, and the actual applicable coverage area of the air-conditioner is the result of the cooling capacity being divided by the cooling load.
AUX air conditioner service manual The rating current (A) of The section area of the plastic insulated leads (mm²) the air-conditioner Copper core Aluminum core (As per the nameplate) <=6 1(1.5) 2.5 6-10 1.5(2.5) 2.5 10-16 2.5(4) 4 16-25 4(6) 6 25-35 6 10 Note: ①Aluminum leads are not recommended in use; ②Larger section area shall be better in use as recommended The division of the ammeters, such as doubleness ammeter、quadruple ammeter etc.
AUX air conditioner service manual air-conditioner. Although the unit “W” is same as the one used for the cooling capacity, they have different practice signification: As we all know 1Hp=735.499W, which stands for the consumption power of the compressor, but the cooling capacity indicates the quantity of heat absorbed from the room by air-conditioner within a unit time.
AUX air conditioner service manual 20dB 30dB 40dB 50dB 60dB Table1-7 the noise to the sense of the human beings: Silence Broadcasting room with nobody in Very quiet The odium with nobody in Almost insensible to the noise Inside the quiet library Feel the noise The quiet hotel hall quite sensible to the noise The ordinary dining room of the plant ⒂ 3C Certification: It’s the abbreviation of China Compulsory Certification, which is aiming to test and evaluate the electrical safety (and structural safety et
AUX air conditioner service manual Section three the basic structure of the air-conditioner Air-conditioner is the kind of machine that performs the function of cooling and heating by utilizing the heat-absorbing and heat-releasing consequence caused by the state variation of the refrigerant. Although there are kinds of models, the working theory and the main structuring parts are basically the same.
AUX air conditioner service manual ② Rotary type The electric motor of the Rotary type compressor is on its top, and the compressor is at the bottom. The whole cylinder almost soaked in the freezing oil completely. The rotor inside the cylinder rolls on the surface of the cylinder wall with the guide of the eccentric shaft. There is a through groove on the surface of the cylinder wall, which contains a slide.
AUX air conditioner service manual air-inlet pipe, “J” air-vent pipe and the pole sleeve. There is no connection between two pipes. The separator is connected with the compressor by the air-inlet pipe. The filter net at the entrance of the separator has the function of gas & liquid separating, noisy eliminating and filtering. Passing through the air-inlet pipe, the refrigerant from the evaporator flows into the separator.
AUX air conditioner service manual a) Evaporator: Evaporator is also called cooler. It is the apparatus used for direct cooling purpose in the refrigerating cycle and is usually installed inside the indoor unit. The evaporator applied in the air-conditioner is the wing coil type with high heat transmission coefficient and compact structure. The liquid refrigerant flows into the snake copper pipe after the throttle of the capillary tubes.
AUX air conditioner service manual For the purpose of enhancing the heat exchange coefficient of the condenser, the number of the wings can be increased or the interval distance between the wings can be shortened. Because there is no condensing water being produced by the wings of the condenser, and there is no much air resistance as the evaporator faces, the distance between the wings can be shortened accordingly.
AUX air conditioner service manual To the air-conditioner with a large evaporating surface area, usually, the coil pipes of the evaporator are ranked together side by side. For enhancing the evaporation efficiency, the liquid distributor is in need to be assembled for having the refrigerant enter into the evaporator equably in various routes. The liquid distributor of the air-conditioner generally consists of a coniform unit body and a throttling nozzle.
AUX air conditioner service manual The electromagnetic reversing valve consists of two parts. One is the solenoid guiding valve; the other one is four- way commutating valve. The solenoid guiding valve usually controls the four-way valve by three guiding capillary tubes.
AUX air conditioner service manual heat exchanger (as condenser) for heat transmission process passing through pipe C, and enters into the indoor heat-exchanger (evaporator) passing through capillary tube. Finally, it will enter into pipe S from pipe E and return back to the compressor for concluding a refrigerating cycle.
AUX air conditioner service manual ②one-way Valve Check valve is also called anti-reverse valve. it permits the refrigerant to flow in only one direction in the refrigeration system, and to be installed in the pipes for preventing process flow from reversing. It is mainly applied in the heat pump air-conditioner and adopted as the assistant to the electromagnetic reversing valve for changing the refrigerant’s flow direction and the system’s pressure.
AUX air conditioner service manual It’s not reliable to rely on the electromagnetic reversing valve only for controlling the flow direction of the refrigerant due to great disparity existing in the working conditions between the cooling and heating modes of the heat pump air conditioner.
AUX air conditioner service manual outdoor units. Inside the position regulator entry, there are valve rod and valve hole seat. A graphite cotton rope (or oil-proof rubber) sealing ring is fixed at the middle position of the valve rod and impacts the valve rod by the force of the fastening screw so as to prevent the gas leaking from the valve rod. Before inspection or installation, screw off the copper enveloping cap, and screw off the fastening screw of the valve rod by the inner hexagonal spanner.
AUX air conditioner service manual The pressure switch used for the air-conditioner includes two types: high pressure switch and low pressure switch. They are composed of the screw joint entry, thin shell film flake, dynamic contact point, static contact point and mandril etc. Such as the picture 2-16: The high pressure switch is fixed at the high pressure side of the refrigerating system.
AUX air conditioner service manual ⑽The other parts: 30
AUX air conditioner service manual Chapter 2 Section one Introduction of AUX products the basic functions introduction of Electric controller Ⅰ.The characteristics of the appearance and structure 1. The appearance photos of the outdoor unit outdoor unit 1 outdoor unit 2 outdoor unit 3 2. The appearance photos of the remote controller (applicable for Model 9000BTU~24000BTU ) YK(R)-F/001E( YKR-F/002E ) YK(R)-C/02JE YK(R)-C/01E Ⅱ.
AUX air conditioner service manual ⑷The air vane’s automatic swing function and the position setting function; ⑸The buzzer’s driving function; ⑹The indoor fan’s driving function; ⑺The timing on-off function; ⑻The compressor restarting protection function; ⑼The indoor heat-exchanger overheating protection function under heating mode; ⑽The automatic defrosting and resume function under heating mode; ⑾The anti-cold air function under heating mode; ⑿The anti-freezing function under cooling and defrosting modes
AUX air conditioner service manual protection), the wind speed of the indoor fan is high wind, the running mode is cooling mode, and the wind door is maximum opening. b) There are no anti-freezing protection and high temperature-preventing protection during trial operation.
AUX air conditioner service manual ⑧Automatic wind-speed control: TA - TS≥3℃,wind-speed works in high wind; TS +1℃≤TA<TS +3℃,wind-speed works in middle wind; TA – TS<1℃,wind-speed works in low wind; Without 3 minutes delay when the wind speed turns from the high wind from the low wind, otherwise with 3 minutes delay; ⑨Being initially electrified, the compressor doesn’t have the 3 minutes extension/delay protection, the outdoor fan starts after 2 seconds of the compressor’s start; TS>TA set by the remote co
AUX air conditioner service manual ⑹Ventilation mode Under ventilation mode, the outdoor unit is always off, and the indoor fan runs according to the default wind-speed. The remote control can be set with three types wind-speed, e.g. high fan, low fan and silent fan except the strong fan; The operation condition of the air door is same as the one under the refrigeration mode; The mode includes the function of timing, auto-restart (optional), negative ion (optional), I feel(optional).
AUX air conditioner service manual ⑨Anti cold-wind and Residual-heat Removing function: TE controls the wind speed of the indoor fan, and the specific conditions are as below: ●The anti cold-wind status when the compressor runs: a) When TE in rise status and at the moment of TE<TE1,the indoor fan turns off;TE2≤TE<TE3, the indoor fan blows the breeze; TE3≤TE<TE4,the indoor fan blows the mute wind; TE≥TE4,the indoor fan blows the set wind speed; b)When TE in fall status and at the moment of TE>TE5,the indoor
AUX air conditioner service manual indoor fan stops immediately. ⑩Overheated protection: a)When heating function runs,if TE≥TE9 and last for 10seconds,the outdoor fan stops;if TE≥TE10 and last for 10seconds, then stop the compressor;When TE< TE11 and after the 3 minutes protection delay, the compressor resumes normal working. b).This temperature protection is valid only when the TE temperature sensor runs normally.
AUX air conditioner service manual the temperature difference correction value shall be -1℃,if the wind speed of the indoor fan rises by one gear, the temperature difference correction value shall be +1℃. ● a)The accumulated operation time of the compressor≥3hour; b)The continuous operation time of the compressor≥20 minutes; c) The difference value between TE and TA less than Y℃.
AUX air conditioner service manual The sleeping process under cooling mode: Setting temperature rises another 1℃ rises 1℃ Previous Setting temperature 1h 2h 7h(end sleeping process,turn off) The sleeping process under heating mode: Setting temperature Previous setting temperature falls 2℃ Falls another 2℃ 1h 2h 7h(end sleeping process,turn off) ⑾Timing control function ①The longest Timing time is 24 hour and to be counted per minute, single timing method, the timing function will not be cancelled due
AUX air conditioner service manual light on 1 second ÆSleep light on 1 second ÆEach phase of the stepping motor’s motion in 1 second Æthe indoor fan runs for 1 second at low fan speed and middle fan speed separatelyÆthe compressor’s motion for 1 second ÆThe four-way valve’s motion for 1 second ÆOutdoor fan’s motion for 1 second ÆNegative generator’s motion for 1 second Æbuzzer deliver one short toneÆElectric heating runs 30 Seconds and stops, then the air conditioner turns into waiting status, the self-det
AUX air conditioner service manual swing, the swing angle will never change; ⑥After turning off the air-conditioner and stopping the running of the indoor fan, the air door shut off automatically; ⑦Enter into the automatic mode by pressing the Emergency button, the air door opens after the setting mode of the system starts. Before the starting of the setting mode, the air door parks at the datum mark of cooling mode.
AUX air conditioner service manual equipped with the corresponding E2 main chip, the “I feel” function shall be equipped with the corresponding remote controller, and the “Negative ion” shall be equipped with the corresponding relay.
AUX air conditioner service manual Ⅲ.The basic function introduction of the split wall-mounted type Electric controller (18000BTU~24000BTU) 1.
AUX air conditioner service manual b) When 20℃< TA < 27℃, the controller enters into the dehumidifying mode and follows the mode in working. The setting temperature is 24℃ and the setting wind speed is strong wind; c) When TA≤20℃, the controller enters into the heating mode and follows the mode in working (The cooling only type runs with the ventilation mode).
AUX air conditioner service manual 16℃ - 32℃. The setting temperature can be adjusted through the button of “+” “-”. The setting wind speed can be adjusted through the button of “wind speed selection” in the selection of the four wind speeds type, such as strong wind, high wind, low wind and mute wind. The four-way valve always is closed under this mode.
AUX air conditioner service manual ②Under the dehumidification mode, after the 3 minutes delay conditions being meet satisfactorily, the performance of the compressor and the outdoor fan is as following: a)TA ≥ TS+2℃,the compressor and the outdoor fan works continuously, the wind speed retains the setting wind speed; b) TS ≤ TA < TS+2℃,the compressor and the outdoor fan runs for 10minutes and stops for 6 minutes,The indoor fan turns off during the compressor’s 3 minutes stopping period and keeps on working
AUX air conditioner service manual ⑺Heating mode The setting temperature can be decided and adjusted by the remote control within the control range of 16℃ - 32℃ through the button of temp. Add “+” and temp. Reduce “-”. Press the button “wind speed option” to choose the wind speed among the options of automatic fan, high fan, middle fan and mute fan.
AUX air conditioner service manual Anti-cold wind when compressor runs: ①When TE is in rise status, if Te<30℃,the indoor fan turns off;30℃≤TE<38℃,the indoor fan runs at low fan speed;Te≥38℃, the indoor fan runs at setting wind speed; ②When Te in fall status, if TE>34℃,the indoor fan runs at the setting fan speed;28℃<TE≤34℃,the indoor fan runs at the low fan speed;TE≤28℃,the indoor fan turns off.
AUX air conditioner service manual the 10second of process of residual heat removal, if TE< 35℃, the indoor fan turns off at once. ⑾Anti-high temperature protection: ①when run on Heating mode,if TE≥57℃ and continuously last 10 seconds, the outdoor fan stops; if TE≥64℃ and last for 10s,the compressor stops again;When TE< 52℃ and satisfying 3minutes protection delay condition, the compressor resume normal work.。 ②Such temperature protection is valid only if the TE sensor works normally.
AUX air conditioner service manual ④The auxiliary electric heating may be allowed to restart after 1 minutes rest if the auxiliary electric heating quit during the operation process of the compressor. ⑼ Sleeping control function The sleeping function is valid during the automatic, cooling, dehumidifying and heating process.
AUX air conditioner service manual The timing turns off function can be set only under the running status of the air-conditioner. The timing range is 1min.-24hour. The air-conditioner stops automatically once the setting timing reached. ②Timing turns on The timing turns on function can be set only under the running status of the air-conditioner. The timing range is 1min.-24hour. The air-conditioner turns on automatically once the setting timing reached.
AUX air conditioner service manual (Picture 3)It shows the swing angles of the types 18000BTU and 24000BTU stepping motor,the air door’s swing angle of 18000BTU,24000BTU and 7000BTU,12000BTU are same,but the swing directions of the motors are not same. ①Once being electrified, the air door effect a motion of totally closed, and the swinging speed is 1 step/4ms; ②After the air-conditioner turns on, the air door effect a motion of total opening, and swing to the corresponding primary position.
AUX air conditioner service manual 18000BTU-24000BTU are RP plastic-sealed motor, the rotate speed can not be controlled by the PCB. ⒂Optional functions The below functions’ programs are already write into the Main chip of the PCB, and can be performed if only the corresponding hardware is available. For example: the E2 CMOS chip is in need for the Auto-restart function, the corresponding remote control is in need for the I feel function, and the relay is in need for the Negative ion function.
AUX air conditioner service manual When the indoor fan is working, press the negative ion function button on the remote control, and the negative ion relay in the controller turns on for starting the output of the negative ions; When the negative ion function is on, press the negative ion function button on the remote control, and the negative ion relay in the controller turns off for stopping the output of the negative ion; 54
AUX air conditioner service manual Section two the tech. parameter of part products 1、Parameter for R22 、H Series、208-230V/60HZ products ASW-09A2/H# ASW-H09A2/H# Model Indoor Outdoor Indoor Outdoor Item Input Performance Type ASW-H12A2/H# Indoor Indoor Outdoor Outdoor Wall -mounted Wall -mounted Wall -mounted Wall -mounted Cooling capacity Kw 2.5 2.5 3.2 3.2 Heating capacity Kw / 2.8 / 3.8 Dehumidifying Kg/h 1.0 1.0 1.2 1.
AUX air conditioner service manual Rated Heating test condition Indoor unit: DB:20℃, WB:------ Outdoor unit: DB:7℃, WB:6℃ Max. Cooling test condition Indoor unit: DB:32℃, WB:23℃ Outdoor unit: DB:43℃, WB:26℃ Max.
AUX air conditioner service manual Rated Cooling test condition Indoor unit: DB:27℃, WB:19℃ Outdoor unit: DB:35℃, WB:24℃ Rated Heating test condition Indoor unit: DB:20℃, WB:------ Outdoor unit: DB:7℃, WB:6℃ Max. Cooling test condition Indoor unit: DB:32℃, WB:23℃ Outdoor unit: DB:43℃, WB:26℃ Max.
AUX air conditioner service manual Protection equipment / EXTERNAL / EXTERNAL / EXTERNAL / EXTERNAL Rated Cooling test condition Indoor unit: DB:27℃, WB:19℃ Outdoor unit: DB:35℃, WB:24℃ Rated Heating test condition Indoor unit: DB:20℃, WB:------ Outdoor unit: DB:7℃, WB:6℃ Max. Cooling test condition Indoor unit: DB:32℃, WB:23℃ Outdoor unit: DB:43℃, WB:26℃ Max.
AUX air conditioner service manual Refrigerant/Charge (g) R22/1050 Protection equipment / Model Item Performance Input ASW-18B2/E# Outdoor / Inner ASW-H18B2/E# Indoor Outdoor ASW-24B2/E# Indoor Outdoor ASW-H24B2/E# Indoor Outdoor Wall -mounted Wall -mounted Wall -mounted Wall -mounted Cooling capacity Kw 5.3 5.3 7.0 7.0 Heating capacity Kw / 5.8 / 7.7 Dehumidifying Kg/h 2.12 2.12 2.8 2.
AUX air conditioner service manual Rated Heating test condition Indoor unit: DB:20℃, WB:------ Outdoor unit: DB:7℃, WB:6℃ Max. Cooling test condition Indoor unit: DB:32℃, WB:23℃ Outdoor unit: DB:43℃, WB:26℃ Max.
AUX air conditioner service manual Rated Cooling test condition Indoor unit: DB:27℃, WB:19℃ Outdoor unit: DB:35℃, WB:24℃ Max. Cooling test condition Indoor unit: DB:32℃, WB:23℃ Outdoor unit: DB:43℃, WB:26℃ 4、Parameter for R22 、M Series、115V/60HZ products ASW-09A3/M ASW-H09A3/M Model Indoor Outdoor Indoor Outdoor Item Input Performance Type Indoor Outdoor ASW-H12B3/M Indoor Outdoor Wall -mounted Wall -mounted Wall -mounted Wall -mounted Cooling capacity Kw 2.6 2.6 3.5 3.
AUX air conditioner service manual Rated Heating test condition Indoor unit: DB:21.1℃, WB: 15.6℃ Outdoor unit: DB:8.3℃, WB:6.1℃ Max. Cooling test condition Indoor unit: DB:32.2℃, WB:222.8℃ Outdoor unit: DB:43.3℃, WB:25.6℃ Max. Heating test condition Indoor unit: DB:26.7℃, WB:------ 62 Outdoor unit: DB:23.9℃, WB:18.
AUX air conditioner service manual Section three Introductions of the optional functions 1. Intelligent defrosting The defrosting judgment basing on the variety of the indoor coil temperature is more precise than the traditional one basing on the variety of the outdoor coil temperature.
AUX air conditioner service manual 5. Music reminding button Every press on the button derivates the reminding music which is same as the functions of the buttons on the mobile phone. 6. The specification of the sterilization function The dust particles accumulated on the filter net may cause the second pollution to the filter after a certain period in use, which seriously affects the quality of the air.
AUX air conditioner service manual Chapter 3 Exploded views of AUX air-conditioner Section one E series products 1.
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 Detailed part list of ASW-H09A2/ET indoor unit Chinese Name Name Material 面板组件 Panel 杀菌过滤网 Anti-bacterial Filter 维 C 防螨过滤网 Vitamin-C & Anti-mites Filter 过滤网组件 Filter 螺钉盖 Screw cover 中框盖 Cover of medium frame 中框组件 Medium frame 导风门 Horizontal air blade 导风叶片 Vertical air blade 导风架 Air blade holder 步进电机组件 Step motor 贯流风叶组件 Indoor fan 橡胶轴承座 Rubber bearing 蒸发器左支架 Left plast
AUX air conditioner service manual Outdoor unit exploded view 70
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 Detailed part list of ASW-H09A2/ET outdoor unit Chinese Name Name Material 面板网罩 Steel grille 面板组件 Front panel 顶盖板 Top cover board 轴流风叶 Outdoor fan 室外电机 Outdoor fan motor 电机架 Motor bracket 冷凝器组件 Condenser assembly 冷凝器进气管 Condenser gas inlet tube 毛细管组件 Capillary assembly 后钢丝网罩 Backside steel grille 电器盖板 Handle 右侧板 Right-side plate 电容抱攀 Capacitor clamp 风机电容 Fan motor capacitor 压缩机电容 Compressor
AUX air conditioner service manual 2.
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 Detailed part list of ASW-H09A2/ET indoor unit Chinese Name Name Material 面板组件 Panel 杀菌过滤网 Anti-bacterial Filter 维 C 防螨过滤网 Vitamin-C & Anti-mites Filter 过滤网组件 Filter 螺钉盖 Screw cover 中框盖 Cover of Medium frame 中框组件 Medium frame 导风门 Horizontal air blade 导风叶片 Vertical air blade 导风架 Air blade holder 步进电机组件 Step motor 贯流风叶组件 Indoor fan 橡胶轴承座 Rubber bearing 蒸发器左支架 Left plastic
AUX air conditioner service manual Outdoor unit exploded view 74
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 Detailed part list of ASW-H09A2/EC outdoor unit Chinese Name Name Material 面板网罩 Steel grille 面板组件 Front panel 顶盖板 Top cover board 轴流风叶 Outdoor fan 室外电机 Outdoor fan motor 电机架 Motor bracket 冷凝器组件 Condenser assembly 冷凝器进气管 Condenser gas inlet tube 毛细管组件 Capillary assembly 后钢丝网罩 Backside steel grille 电器盖板 Handle 右侧板 Right-side plate 电容抱攀 Capacitor clamp 风机电容 Fan motor capacitor 压缩机电容 Compressor
AUX air conditioner service manual 3.
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 Detailed part list of ASW-H12A2/ET indoor unit Chinese Name Name Material 面板组件 Panel 杀菌过滤网 Anti-bacterial Filter 维 C 防螨过滤网 Vitamin-C & Anti-mites Filter 过滤网组件 Filter 螺钉盖 Screw cover 中框盖 Cover of medium frame 中框组件 Medium frame 导风门 Horizontal air blade 导风叶片 Vertical air blade 导风架 Air blade holder 步进电机组件 Step motor 贯流风叶组件 Indoor fan 橡胶轴承座 Rubber bearing 蒸发器左支架 Left plast
AUX air conditioner service manual Outdoor unit exploded view 78
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 Detailed part list of ASW-H12A2/ET outdoor unit Chinese Name Name Material 面板网罩 Steel grille 面板组件 Front panel 顶盖板 Top cover board 轴流风叶 Outdoor fan 室外电机 Outdoor fan motor 电机架 Motor bracket 冷凝器组件 Condenser assembly 冷凝器进气管 Condenser gas inlet tube 毛细管组件 Capillary assembly 后钢丝网罩 Backside steel grille 电器盖板 Handle 右侧板 Right-side plate 电容抱攀 Capacitor clamp 风机电容 Fan motor capacitor 压缩机电容 Compressor
AUX air conditioner service manual 4.
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 Detailed part list of ASW-H12A42EC indoor unit Chinese Name Name Material 面板组件 Panel 杀菌过滤网 Anti-bacterial Filter 维 C 防螨过滤网 Vitamin-C & Anti-mites Filter 过滤网组件 Filter 螺钉盖 Screw cover 中框盖 Cover of Medium frame 中框组件 Medium frame 导风门 Horizontal air blade 导风叶片 Vertical air blade 导风架 Air blade holder 步进电机组件 Step motor 贯流风叶组件 Indoor fan 橡胶轴承座 Rubber bearing 蒸发器左支架 Left plastic
AUX air conditioner service manual Outdoor unit exploded view 82
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 Detailed part list of ASW-H12A2/EC outdoor unit Chinese Name Name Material 面板网罩 Steel grille 面板组件 Front panel 顶盖板 Top cover board 轴流风叶 Outdoor fan 室外电机 Outdoor fan motor 电机架 Motor bracket 冷凝器组件 Condenser assembly 冷凝器进气管 Condenser gas inlet tube 毛细管组件 Capillary assembly 后钢丝网罩 Backside steel grille 电器盖板 Handle 右侧板 Right-side plate 电容抱攀 Capacitor clamp 风机电容 Fan motor capacitor 压缩机电容 Compressor
AUX air conditioner service manual 5.
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Detailed part list of ASW-H18B2/ET indoor unit Chinese Name Name Material 面板组件 Panel 大扁头自攻螺钉 Screw 电控盒盖 Cover of medium frame 螺钉盖 Screw cover 大扁头自攻螺钉 Screw 导风门 A Horizontal air blade A 导风门 B Horizontal air blade B 导风门连杆 Connection-pole of horizontal air blade 步进电机组件 Step motor 十字槽自攻螺钉 Screw 大扁头自攻螺钉 Screw 压线板 Wiring clamping cover 导风架组件 Air blade holder 控制器总成 Electric controller assembly 抽头塑封电机组件 Indoor fan
AUX air conditioner service manual Outdoor unit exploded view 86
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 Detailed part list of ASW-H18B2/ET outdoor unit Chinese Name Name Material 左侧支撑板 Left-side supporting plate 钢丝网罩 Steel grille 大扁头自攻螺钉 Screw 顶盖板 Top cover board 大面板 Front panel 冷凝器总成 Condenser assembly 右侧板 Right-side panel plate 小挖手 Handle 电容抱攀 Capacitor clamp 压缩机电容 Compressor capacitor 电机电容 Fan motor capacitor 压线板 Wiring clamping cover 电器架 Electrical holding plate 五位端子板 Terminal board 隔风立板 Partiti
AUX air conditioner service manual 6.
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Detailed part list of ASW-H24B2/ET indoor unit Chinese Name Name Material 面板组件 Panel 大扁头自攻螺钉 Screw 电控盒盖 Cover of medium frame 螺钉盖 Screw cover 大扁头自攻螺钉 Self-drill screw 导风门 A Horizontal air blade A 导风门 B Horizontal air blade B 导风门连杆 Connection-pole of horizontal air blade 步进电机组件 Step motor 十字槽自攻螺钉 Screw 大扁头自攻螺钉 Screw 压线板 Wiring clamping cover 导风架组件 Air blade holder 控制器总成 Electric controller assembly 抽头塑封电机组件
AUX air conditioner service manual Outdoor unit exploded view 90
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 Detailed part list of ASW-H24B2/ET outdoor unit Chinese Name Name Material 左侧支撑板 Left-side supporting plate 钢丝网罩 Steel grille 大扁头自攻螺钉 Screw 顶盖板 Top cover board 大面板 Front panel 冷凝器总成 Condenser assembly 右侧板 Right-side panel plate 小挖手 Handle 电容抱攀 Capacitor clamp 压缩机电容 Compressor capacitor 单极交流接触器 AC Contactor 电机电容 Fan motor capacitor 压线板 Wiring clamping cover 电器架 Electrical holding plate 五位端子板 Ter
AUX air conditioner service manual Section two H series products 1.
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Detailed part list of ASW-H09A2/HSF indoor unit Chinese Name Name Material 面板组件 Panel 过滤网组件 Filter 电器盖板 Cover of medium frame 中框盖 Medium frame 导风门 Horizontal air blade 导风叶片 Vertical air blade 导风架 Air blade holder 步进电机组件 Step motor 贯流风叶组件 Indoor fan 橡胶轴承座 Rubber bearing 蒸发器左支架 Left plastic crutch for evaporator 蒸发器总成 Evaporator assembly 底座组件 Chassis 挂板组件 Mounting plate 管路压板 Tube clamp p
AUX air conditioner service manual Outdoor unit exploded view 94
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 Detailed part list of ASW-H09A2/HSF outdoor unit Chinese Name Name Material 面板网罩 Steel grille 面板组件 Front panel 顶盖板 Top cover board 轴流风叶 Outdoor fan 室外电机 Outdoor fan motor 电机架 Motor bracket 冷凝器组件 Condenser assembly 冷凝器进气管 Condenser gas inlet tube 毛细管组件 Capillary assembly 后钢丝网罩 Backside steel grille 电器盖板 Handle 右侧板 Right-side plate 电容抱攀 Capacitor clamp 风机电容 Fan motor capacitor 压缩机电容 Compressor
AUX air conditioner service manual 2.
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Detailed part list of ASW-H09A2/HSL indoor unit Chinese Name Name Material 面板组件 Panel 过滤网组件 Filter 电器盖板 Cover of medium frame 中框盖 Medium frame 导风门 Horizontal air blade 导风叶片 Vertical air blade 导风架 Air blade holder 步进电机组件 Step motor 贯流风叶组件 Indoor fan 橡胶轴承座 Rubber bearing 蒸发器左支架 Left plastic crutch for evaporator 蒸发器总成 Evaporator assembly 底座组件 Chassis 挂板组件 Mounting plate 管路压板 Tube clamp p
AUX air conditioner service manual Outdoor unit exploded view 98
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 Detailed part list of ASW-H09A2/HSL outdoor unit Chinese Name Name Material 面板网罩 Steel grille 面板组件 Front panel 顶盖板 Top cover board 轴流风叶 Outdoor fan 室外电机 Outdoor fan motor 电机架 Motor bracket 冷凝器组件 Condenser assembly 冷凝器进气管 Condenser gas inlet tube 毛细管组件 Capillary assembly 后钢丝网罩 Backside steel grille 电器盖板 Handle 右侧板 Right-side plate 电容抱攀 Capacitor clamp 风机电容 Fan motor capacitor 压缩机电容 Compressor
AUX air conditioner service manual 3.
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Detailed part list of ASW-H09A2/HS indoor unit Chinese Name Name Material 面板组件 Panel 过滤网组件 Filter 电器盖板 Cover of medium frame 中框盖 Medium frame 导风门 Horizontal air blade 导风叶片 Vertical air blade 导风架 Air blade holder 步进电机组件 Step motor 贯流风叶组件 Indoor fan 橡胶轴承座 Rubber bearing 蒸发器左支架 Left plastic crutch for evaporator 蒸发器总成 Evaporator 底座组件 Chassis 挂板组件 Mounting plate 管路压板 Tube clamp plate 塑封电机组
AUX air conditioner service manual Outdoor unit exploded view 102
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 Detailed part list of ASW-H09A2/HS outdoor unit Chinese Name Name Material 面板网罩 Steel grille 面板组件 Front panel 顶盖板 Top cover board 轴流风叶 Outdoor fan 室外电机 Outdoor fan motor 电机架 Motor bracket 冷凝器组件 Condenser assembly 冷凝器进气管 Condenser gas inlet tube 毛细管组件 Capillary assembly 后钢丝网罩 Backside steel grille 电器盖板 Handle 右侧板 Right-side plate 电容抱攀 Capacitor clamp 风机电容 Fan motor capacitor 压缩机电容 Compressor
AUX air conditioner service manual 4.
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Detailed part list of ASW-H18B2/HS indoor unit Chinese Name Name Material 过滤网组件 Filter 螺钉盖 Screw cover 中框组件 Medium frame 导风门 Horizontal air blade 导风叶片 Vertical air blade 导风架 Air blade holder 蒸发器左支架 Left plastic crutch for evaporator 蒸发器总成 Evaporator 橡胶轴承座 Rubber bearing 贯流风叶 indoor fan 底座组件 Chassis 挂板组件 Mounting plate 管路压攀 Pipe clamp 塑封电机 Indoor fan motor 电控盒 Electric controller box 变压器 Transformer 端子板 Ter
AUX air conditioner service manual Outdoor unit exploded view 106
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 Detailed part list of ASW-H18B2/HS outdoor unit Chinese Name Name Material 左侧支撑板 Left-side supporting plate 钢丝网罩 Steel grille 大扁头自攻螺钉 Screw 顶盖板 Top cover plate 大面板 Front panel 冷凝器总成 Condenser assembly 右侧板 Right-side plate 小挖手 Handle 电容抱攀 Capacitor clamp 压缩机电容 Compressor capacitor 风机电容 Fan motor capacitor 压线盖 Wiring cover 电器架 Electrical holding plate 五位端子板 Terminal board 隔风立板组件 Partition plate 压缩机组
AUX air conditioner service manual 5.
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Detailed part list of ASW-H24B2/HS indoor unit Chinese Name Name Material 过滤网组件 Filter 螺钉盖 Screw cover 中框组件 Medium frame 导风门 Horizontal air blade 导风叶片 Vertical air blade 导风架 Air blade holder 蒸发器左支架 Left plastic crutch for evaporator 蒸发器总成 Evaporator 橡胶轴承座 Rubber bearing 贯流风叶 Indoor fan 底座组件 Chassis 挂板组件 Mounting plate 管路压攀 Pipe clamp 塑封电机 Indoor fan motor 电控盒 Electric controller box 变压器 Transformer 端子板 Ter
AUX air conditioner service manual Outdoor unit exploded view 110
AUX air conditioner service manual No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 Detailed part list of ASW-H24B2/HS outdoor unit Chinese Name Name Material 左侧支撑板 Left-side supporting plate 钢丝网罩 Steel grille 大扁头自攻螺钉 Screw 顶盖板 Top cover plate 大面板 Front panel 冷凝器总成 Condenser assembly 右侧板 Right-side plate 小挖手 Handle 电容抱攀 Capacitor clamp 压缩机电容 Compressor capacitor 单级交流接触器 AC Connector 风机电容 Fan motor capacitor 压线盖 Wiring clamping cover 电器架 Electrical holding plate 五位端子板 Terminal
AUX air conditioner service manual Section 3 Exploded View of M Series (9000-12000Btu/h) 1.
AUX air conditioner service manual Detailed part list of M series indoor unit No Name of part Remark 1 Hanging board assembly 2 Chassis 3 Clamping prop for tube line 4 Bearing for air leaves 5 Through-flow fan leaves 6 Plastic-sealed electric motor 7 Left-hand propping holder for vaporizer 8 Vaporizer assembly 9 Light holder for indicator 10 Wind guide board 11 Step-by-step electric motor 12 Water-draining tube assembly 13 Louver 14 Inner frame 15 Cover for electric control
AUX air conditioner service manual 2.
AUX air conditioner service manual Detailed part list of the outdoor unit (Cooling only Type) No Name of part remark 1 Top cover 2 Cover for electric unit 3 Right-hand board 4 Condenser assembly 5 Holder for electric motor 6 Outdoor electric motor 7 Axial-flow wind leaves 8 Holder for wiring 9 Capacitor for compressor 10 Capacitor for electric motor 11 Terminal board 12 Clamping plate for power connection line 13 Panel 14 Net for panel 15 Chassis assembly 16 Valve panel 1
AUX air conditioner service manual 116
AUX air conditioner service manual Detailed part list of the outdoor unit (Heat pump Type) No Name of part remark 1 Top cover 2 Cover for electric unit 3 Right-hand board 4 Condenser assembly 5 Holder for electric motor 6 Outdoor electric motor 7 Axial-flow wind leaves 8 Holder for wiring 9 Capacitor for compressor 10 Capacitor for electric motor 11 Terminal board 12 Clamping plate for power connection line 13 Panel 14 Net for panel 15 Chassis assembly 16 Valve panel 18
AUX air conditioner service manual Chapter 4 The disassembly and the relating attention issues to the part of AUX product Section one the disassembly and the relating attention issues to the series products of 9000BTU~12000BTU Attention: Turn off the air-conditioner and pull out the plug of the power supply before the service. 1. Indoor unit: No. Part Panel 1 1) 2) 3) 4) 5) Operation Process Turn off the air-conditioner and cut off the power supply; Tear the adhesive tape sticking to the panel.
AUX air conditioner service manual No. 2 Part Operation Process Electrical 1) Do No. “1” firstly; component 2) Pull out all tie-in connecting with PCB and the temperature sensor, etc.; 3) Screw off the screws and bolts as indicated in the picture. Untie the outdoor unit’s interconnection cord and power supply cord from the terminal of the electrical box. 4) If the main PCB board is loosed by chance, remove it away; 3 Water draining tank 4 Evaporator 1) Do No.”1” , “2” and “3” firstly; 1) Do No.
AUX air conditioner service manual 2. Outdoor unit: No.
AUX air conditioner service manual No. 3 Part Condenser Operation Process 1) Do No.”1” and “2” firstly; 2) Screw off the two fastening bolts; 3) Weld off the inlet and outlet tube; 4) Offload the condenser. 4 Compressor 1) Do No.”1” , “2”and “3” firstly; 2) Open the cover of compressor, release the connection cord. 3) Weld off the inlet and outlet tube; 4) Screw off the three screws; 5) Offload the compressor.
AUX air conditioner service manual Section Two the disassembly and the relating attention issues to the series product of 18000BTU~24000BTU Attention: Turn off the air-conditioner and pull out the plug of the power supply before the service. 2. Indoor unit: No. Part 1 Front panel Operation Process 1) Turn off the air-conditioner and cut off the power supply; 2) Remove the adhesive tape sticking to the panel.
AUX air conditioner service manual No. 2 Part Operation Process Electrical 1) Do No. “1” firstly; component 2) Pull out all tie-in connecting with PCB and the temperature sensor, etc.; 3) Screws off the screws and bolts at the three positions indicated in the picture. Untie the outdoor unit’s interconnection cord and power supply cord from the terminal of the electrical box.
AUX air conditioner service manual 2. Outdoor unit No.
AUX air conditioner service manual No.
AUX air conditioner service manual Chapter 5 Troubleshooting and electrical chart of AUX air conditioner Section one basic faults diagnose process of 9000BTU~12000BTU products Troubleshooting Guide 1. The Foremost Inspecting Items ⑴The input voltage must be within +10% tolerance of the rated Voltage. If it is not the case, the air-conditioner will probably not work normally. ⑵Check the connecting cord between indoor unit and outdoor unit to see if it is properly connected.
AUX air conditioner service manual 3.
AUX air conditioner service manual 4.
AUX air conditioner service manual 5. The Step Motor Does Not Work ⑴Items a) Check if the input voltage is correct? b) Check if the step motor controlling the up-down movement firmly connected to Cn2? ⑵Trouble shooting procedure 6.
AUX air conditioner service manual 7. Remote Control Can Not Work Trouble shooting procedure 8.
AUX air conditioner service manual 131
AUX air conditioner service manual Section two basic faults diagnose process of 18000BTU~24000BTU products Troubleshooting Guide 1. The Foremost Inspecting Items ⑴The input voltage must be within +10% tolerance of the rated Voltage. If it is not the case, the air-conditioner will probably not work normally. ⑵ Check the connecting cord between indoor unit and outdoor unit to see if it is properly connected.
AUX air conditioner service manual 3.
AUX air conditioner service manual 4.
AUX air conditioner service manual 5. The Step Motor Does Not Work ⑴Items ①Check if the input voltage is correct? ②Check if the step motor controlling the up-down movement firmly connected to Cn2? ⑵Trouble shooting procedure 6.
AUX air conditioner service manual 7. Remote Control Can Not Work Trouble shooting procedure 8.
AUX air conditioner service manual Section three Electric wiring diagram of AUX air conditioner 1.
AUX air conditioner service manual ⑵ Outdoor unit: Fan Motor Black Fa n Mo to r Ca pac it or Re d Br ow n O rientation Valve Wh it e O ver curr ent Pr otector Co mpressor Black Black Re d Blu e Re d Blue Yellow G ree n Ye llow Co mpr e sso r Ca pa cit o r 1 Red 2 Y /G 4 5 Yellow Blac k G reen Blue Br ow n To In do o r Un it Fan Motor Black R ed Fa n Mo to r C a pa cito r B r ow n W h ti e O ver curr ent Pr otec tor Compr essor Bla ck Black Re d Re d Yellow G reen Ye lo w C
AUX air conditioner service manual 2.
AUX air conditioner service manual ⑵ Outdoor unit: Bla ck Fan Motor Cap acitor W hi te B rown Or ie nta ti o n Valv e R ed Bla ck Com pre s sor Over cur r ent Pr otecto r R ed Blu e Blu e Co mpr e sso r Ca pa cit o r Ye llo w Yellow G reen H eat -P ump Typ e Fo rS er ies Of ( 70 00- 19 00 0 )B tu/h (R) (B) R ed O utdoor U nitElectr ic Char t Y/ G (BL) (BR) Yellow G reen Bla ck Blue Br ow n To Ind oor U nit To In do o r U nit Fa n Mo to r T emp er at u re Sensor θ Fan Motor Bla ck W
AUX air conditioner service manual 3.
AUX air conditioner service manual ⑵ Outdoor unit:(Single pole AC.
AUX air conditioner service manual ⑶ Outdoor unit(Double pole AC.
AUX air conditioner service manual Chapter 6 Introduction of the regular service tools for air-conditioner The regular service tool and application 1. Vacuum Pump Vacuum pump is a device used in vacuumize for the mini type refrigerating equipment. The common vacuum pump in practice is the revolving blade type.
AUX air conditioner service manual There is only one cylinder installed in the Single-stage rotary Vacuum pump. Inside the cylinder, the rotor is eccentrically mounted inside the cylinder. There are two rotary blades fixed inside the rotor groove, and two of them are oppressed tightly to the surface of the cylinder by the central spring force and the centrifugal force produced in the process of rotation.
AUX air conditioner service manual knob of valve in counterclockwise direction may enlarge the size of the valve bore, and the corresponding tubing will get through with the gas path of the outdoor unit. The refrigerating system always gets through with the pressure gauge on the three-way mend valve without concerning the position of the knob. The conjunction with the knob of the three-way mend valve may carry out the process of vacuumizing, refrigerant filling and pressure testing etc.
AUX air conditioner service manual Picture6-4 Expander Picture6-5 Structure of expander 5. Tube-cutting knife The tube-cutting knife is usually used for cutting the copper tubes in different lengths and diameters when repairing or installing the air-conditioner. The types of the tube-cutting knife are various. The common structure is as Picture 6-6 shows. When cutting the copper tube, it shall be set at the place between the two rolling wheels of the tube-cutting knife.
AUX air conditioner service manual 6. Tube bender Tube bender is the tool used to change the configuration of the copper tube or process the copper tube in a certain figure. The types of the tube bender are various and it is applicable in bending the copper tube with the diameter less than 20mm. When bending the tube, insert the annealed copper tube into the wheel groove of the tube bender, and lock the tube clamping hook tightly. Then rotate the handle bar slowly until reaching the required angle.
AUX air conditioner service manual meter pen of the clamp meter can be freely used without consideration of the selection between positive and negative pole. When measuring the direct current voltage, turn the on-off switch to the category of the DCV (DC voltage) , pay attention to select a measurement range larger than the voltage to be measured, and confirm the polarity of the voltage to be measured.
AUX air conditioner service manual Chapter 7 Failure Analysis and Inspection of Electrical Control System Air conditioner can be controlled by both strong-current circuit control panel and weak-current electronic circuit control panel, control philosophies of which are different, so fault analysis procedures of the two types shall be described separately: Electrical system is the device to control and protect refrigerating system and fan system.
AUX air conditioner service manual (5)Heat pump air conditioner fails to heat If air conditioner can produce cooling air but fail to produce heating air, there must be some faults in magnetic reversing valve or switch. ① Magnetic loop of magnetic valve has burnt out or broken out because of: a、 Operate in severe environment; b、Magnetic loop stops and starts up frequently; c、 Operate under excessive voltage for a long time so that loops run under high temperature rise and insulation layer has been damaged.
AUX air conditioner service manual ② ③ ④ ⑤ ⑥ ⑦ ⑧ lower than rated value; Over-current on compressor: check if heat protector on the compressor pump shell has broken off. Normally, heat protector will break off if current is excessively large. Heat protector of three phase motor is embedded in motor winding in pump shell. Check junction box on the pump shell by using universal meter, both for single phase and three phase motor; if winding is current off, protector has cut off the power.
AUX air conditioner service manual three- phase. Single phase motor has two windings, i.e. startup winding and running winding. There’re 3 binding posts, in shell junction box of compressor. They are marked by A, B and C individually, representing running post, startup post and common post.
AUX air conditioner service manual winding touching shell can also occur in three phase motor. Check the faults with universal meter. For star- type connection motor, resistance can be measured individually; for triangle- type connection motor, three windings shall be disconnected before resistance values are measured. 4.
AUX air conditioner service manual a、Commute, demodulation, switch and stabilivolt diode. Remove diode from electrical panel, check its single phase conductivity with R×1K and R×100 of universal meter. Check method: contact two ends of diode with two handles of meter, record the resistance value, then change two handles with each other and measure again. For a normal diode, two resistance values are different greatly; large one is called reverse resistance and the smaller one forward resistance.
AUX air conditioner service manual noise can be heard.
AUX air conditioner service manual Reason Analysis: to check remote controller, point the remote controller to an ordinary radio and push any buttons on it, radio responded, so remote controller worked well, and there must be some faults in main control panel or receiver of remote controller of indoor unit.
AUX air conditioner service manual when indoor temperature sensor and heat exchanger exceed 25 Celsius degree, fan produces gentle wind; when temperature exceeds 38 Celsius Degree, fan produces wind of set velocity. We checked and found that wind velocity is very low, and wind temperature is quite high, so fan works well. So we presumed that the sensor failed to reflect the correct temperature, and then indoor fan can’t run at set velocity, so it must be replaced.
AUX air conditioner service manual the lamp was turned off, air conditioner functioned properly. When lamp was turned on, we checked receiver and found 2V AC electricity on the input end; when we turned out the lamp, and didn’t operate remote controller, there’s no voltage on receiver. Solution: replace fluorescent lamp with product of other brand Experience Conclusion: wave produced by electron rectifier fluorescent lamp may superpose on infrared wave and cause failure of receiver.
AUX air conditioner service manual on plastic panel may deform, so buttons may fail to work. In this case, control panel shall be replaced with same model product. Case 9 Compressor low -pressure can’t be started up Product Model:ASW-H12A4/HS Phenomena:Compressor of outdoor unit can’t be started up Cause Analysis: Indoor unit works well; voltage output and resistance of outdoor compressor are in normal scope, so there’s some problem in compressor.
AUX air conditioner service manual when we’re repairing air conditioners and avoid replicated work. Case 12 Transformer Failure Product Model:ASF-H18A4/FS Phenomena: air conditioner didn’t function after it was turned on Cause Analysis: checked power supply, there’s 220V input power, so power supply circuit has no problem. Checked power socket, resistance is infinite great, so fuse or transformer might burn out.
AUX air conditioner service manual Chapter 8 Troubleshooting guide for Refrigerating System Refrigerating system faults are very common to air conditioners; faults are various but they still have some rules and also many maintenance experiences for reference. Troubleshooting steps here for refrigerating system are not a must, but can be followed to eliminate faults. 1.
AUX air conditioner service manual there is some leak source, refrigerant will leak out and air conditioner can’t cooling proper or absolutely stop refrigerating. Leakage sources locate mainly on welds of evaporator, condenser, and capillary, return gas and discharge tube of compressor, flare mouth, copper nut, connection tubes and etc. Check the air conditioner visually and then inspect joints of tubes carefully. Generally, there’s grease spot on the leakage source.
AUX air conditioner service manual pressure hose with vacuum pump and vacuum the system. ②Tighten thimble head; Discharge air in the hose with refrigerant steam in system or refrigerant in the bottle. If small refrigerant bottle has been connected with hose and vacuum pumping has been done, there’s no need to discharge air. ③Start up air conditioner, check low pressure value when it runs stably and judge the remaining refrigerant in system.
AUX air conditioner service manual shall be no less than 10℃ and in heating operation, temperature difference shall be over 15℃; ⑤ High pressure: High pressure value of cooling operation shall be about 1.5~1.9MPa; ⑥ Weighing: When we fill the air conditioner with refrigerant, we shall weigh refrigerant with electronic weighing appliance if available. It is one best way to add the refrigerant.
AUX air conditioner service manual Pollution degree of refrigerating system can be classified as: slightly polluted and seriously polluted. When system is slightly polluted, condensed oil in it has not been polluted completely, and if refrigerant and lubricant is released from line of compressor, it is transparent and will become light yellow(normally they should be in white) if tested with litmus paper.
AUX air conditioner service manual Generally, system shall be purged under a pressure of 0.6MPa which can be pressurized with refrigerating compressor, nitrogen bottle or air compressor (compressed air can’t be used in Freon system). System shall be blown in sections, with dirt outlet set on the lowest point of each section. Each dirt outlet shall be plugged up with cork (tied with steel wire). When pressure reaches 0.
AUX air conditioner service manual ③、Weld high pressure tube first, and then the middle one of three low pressure tubes, finally left and right tubes; ④、Select proper welding machine, flame shall be adjusted and can weld the valve immediately. Pack the valve body with wet towel to avoid burning rubber and nylon sealing elements in it and causing the leakage of four-way valve. ⑤、;Weld the tube one by one and start welding the second one after the first one cools down.
AUX air conditioner service manual burned or components can’t start up. So clearance scope between pistol and cylinder is very small. For Diaφ50mm cylinder without pistol ring, fit clearance shall be within 0.011~0.018mm.
AUX air conditioner service manual Symptom is: when air conditioner is switched on, fuse protector breaks or air protector trips immediately. There’re three reasons for this symptom: a) Because motor stator windings have burn out, and insulation layer of electromagnetic loop has been broken and windings touch the motor shell and are short circuited.
AUX air conditioner service manual Cause Analysis: turned on the air conditioner, it could run normally. Checked filter of indoor unit and heat exchangers, and found that they were quite clean and wouldn’t impact the cooling efficiency. Checked capacitors and all parameters of indoor and outdoor fans, voltage was 220v, current was 13.5A, low pressure was 0.4MPa and there’s no extension line, outdoor compressor also run normally, in addition, no flow restriction was found.
AUX air conditioner service manual analyze this phenomenon, we shall check whether air flow of indoor unit is sufficient. If it is in normal condition, check whether there’s secondary flow restriction; judge the fault by analyze phenomena carefully.
AUX air conditioner service manual conditioner run 5 minutes, and evaporator of indoor unit was frosted, so we presumed that refrigerant was not sufficient; we checked and found that low pressure was 3KG. Turned off air conditioner, checked indoor & outdoor units and connection tube and found oil stain on the junction of low pressure copper tube.
AUX air conditioner service manual condenser, so refrigerant leaked out. Solution: repair-welded leak source and added refrigerant Experience Conclusion: when air conditioner is running, system pressure is zero, we can judge that refrigerant leaks out; generally, oil stain can be seen on leak sources. Maintenance personnel shall be familiar with blinking conditions of indicator.
AUX air conditioner service manual tubes, the one connecting discharge pipe of compressor was hot, and other three were also a little hot. Turned on the air conditioner in heating mode, heating efficiency was also unsatisfactory. So we were sure that four-way valve had some problems. Solution: replaced four-way valve, vacuum the system to check leakage sources and finally added refrigerant.
AUX air conditioner service manual Experience Conclusion: valve is too tight, so system is obstructed and then frosted. When refrigerating efficiency of new unit was unsatisfactory, do not add refrigerant without careful consideration. Case 15 Air conditioner was blocked by dirt Unit Model:ASW-H41A5/A Phenomena:Poor cooling efficiency, wind velocity didn’t change obviously Cause Analysis: totally 5 cabinet air conditioners were used in a workshop of a Garment Company, which occupied an area of 350m2.
AUX air conditioner service manual Phenomena:Refrigerating efficiency was unsatisfactory, outdoor unit stopped to run after it operated for some time. Cause Analysis: air conditioner was installed last year, and failed to run properly since then. Maintenance personnel checked the air conditioner many times, and had following data: running current was 12.5A, pressure was 5kg.f/com2, inlet wind temperature was 12 Celsius Degree, and outlet wind temperature was 30 Celsius Degree.
AUX air conditioner service manual Case 19 Water entered the system in installation Unit Model:ASW-H12A4/H Phenomena:Air conditioner could be turned on but couldn’t produce cool air Cause Analysis: run air conditioner for 10 minutes, it could cool normally, pressure and current was normal; air conditioner continued to run, low pressure decreased gradually, current also decreased, and cooling efficiency became unsatisfactory, so we presumed water entered system when air conditioner was installed.
AUX air conditioner service manual Chapter 9 Maintenance Cases of Noise and water leakage of AC Section one cases of air conditioner noise reduction Air conditioner noise is a common problem seen in our maintenance work, causes of which shall be paid attention to.
AUX air conditioner service manual presumed that fault was on bearing bush of left blade. Replaced bearing bush, noise could still be heard. Maintenance personnel checked wind blades and found that they’re installed left to the center and blade axis touched rubber seat of bearing and produced noise when running. Solution: move wind blade to right by 2mm and noise was eliminated.
AUX air conditioner service manual Experience Conclusion: the said noise is wind sound, which isn’t beyond noise standard. In such case, do not change motor or controller without careful consideration.
AUX air conditioner service manual Unit Model: ASW-12A4/A Phenomena:Indoor Noise Cause Analysis: the air conditioner was newly installed; according to client, noise of indoor unit was loud. Maintenance personnel of service network visited the client and checked the air conditioner many times and believed the appliance worked well, so client was unhappy. We checked the air conditioner and found that air blades made noise sometimes.
AUX air conditioner service manual tube and sheet-metal. We should install damp piece or insulation sleeve. ⑶ Vibration of compressor causes collision between copper tubes. Install insulation to isolate two tubes. In such case, we should explain to client that it’s not air conditioner fault, it is caused by improper installation and can be handled easily.
AUX air conditioner service manual of two back branches was obviously lower, so system was blocked when it was welded. Released refrigerant, welded the system again and fault was eliminated. Solution: welded the copper tube again, air conditioner run normally Experience Conclusion: generally, air-stream sound was produced by over throttling, so we shall analyze causes for throttling.
AUX air conditioner service manual Unit Model: ASW-H24A4/TB Phenomena:Outdoor unit made loud noise according to client Cause Analysis: according to client, noise made by air conditioner was not so loud in the daytime, but it was much louder at night. We turned on air conditioner; outdoor unit noise could be heard in the room.
AUX air conditioner service manual long time. When evaporator is blocked by ice, fins of U-shaped tubes with large refrigerant flow will be in low temperature, while those with small refrigerant flow will be in higher temperature, so temperature difference between two circuits will be relatively large, which will produce a large number of condensate in the former fins. Condensate is blown outside the outlet with wind.
AUX air conditioner service manual Unit Model: ASW-12A4/M Phenomena:Indoor unit leaked water Cause analysis:air conditioner had been used for two years and never leaked water before, so it was not caused by improper installation, it was possibly caused by obstruction in water drain pipe. When air conditioner worked for a long time, condensate leaked from notch of basement connection tube. We checked the appearance of air conditioner, it was installed on a level plane and filter had been cleaned.
AUX air conditioner service manual Phenomena:Indoor unit leaked water Cause analysis:We turned on air conditioner, found that air pipe of indoor unit leaked, especially on left and right ends. This air conditioner adopted four-folded evaporator, two water collection channels: upper and down, upper channel was on the back of evaporator, where a water barrier guided water to upper channel, condensate flew from two ends of water barrier, which were affixed with sponge, to indoor unit.
AUX air conditioner service manual water couldn’t flow smoothly and water drain tube leaked. Solution: adjusted position of water drain tube.。 Experience Conclusion: pay attention to details during installation and have water drain test after installation. Case 7: Water Drain Tube wasn’t wrapped tightly enough and leaked condensate Unit Model: ASW-07B4/HA Phenomena: After air conditioner run for half an hour, water drain tube of indoor unit was full of condensate and leaked water.
AUX air conditioner service manual Unit Model: ASW-H09A4/A Phenomena:Air conditioner leaked water after running for some time, evaporator was frosted or frozen. Cause Analysis: according to client, indoor unit leaked water. We turned on air conditioner and observed, after 10 minutes, water started to be blown from indoor fan.
AUX air conditioner service manual smooth, and water drain tube could discharge water normally. We opened indoor unit shell, checked and found that evaporator and basement were assembled properly, but there’s a leak between left bracket and left fin of evaporator, which leaked air. Affixed the leak with sponge and turned on air conditioner again. Water leakage was reduced, but fault hadn’t been eliminated.
AUX air conditioner service manual APPENDIX 1 Introduction to the fault display CODE of AUX air conditioner 1. 70S .100S.120S.45T.50T.60T45TA.50TA.60TA.70T1,when the faults happen, the LCD panel displays “fault” and the corresponding code. ⑴ The fault of the indoor plastic temperature sensor: System turns off, the panel displays “E1”. ⑵ The fault of the outdoor tube temperature sensor on the indoor panel: System doesn’t turns off, the panel displays “E2”.
AUX air conditioner service manual short circuit. ⑷ Fault 24 No load. ⑸ Fault 26 Outdoor over-current protection. ⑹ Fault 28 Outdoor voltage abnormal. ⑺ Fault 29 Outdoor electric source’s instant off. ⑻ Fault 2A Outdoor refrigeration’s overloading protection. ⑼ Fault2B Outdoor defrosting display. ⑽ Fault 2C IPM module fault. ⑾ Fault 2d Outdoor E2 data fault. Simultaneously press the key of “hour”, “minute” again and last for 2 seconds. Resume displaying the temperature after the sound of the buzzer.
AUX air conditioner service manual The “running” light and “swing” light are twinkling and last for 0.5/0.5 second, the other indication lights are invariable, and the system turns off. 4. ASF-H24B4/B, ASF-H41A5/B faults display and protection display: ⑴ Fault of the Indoor temperature sensor: System turns off; the panel displays “E1” ⑵ The fault of the outdoor tube temperature sensor on the indoor panel: System doesn’t turn off; the panel displays“E2”.
AUX air conditioner service manual When the faults happen, the LED digital screen of the operation panel displays the corresponding code. ⑴ Fault of The indoor temperature sensor: System turns off, and the LED digital screen of the operation panel displays “E1”. ⑵ Fault of the outdoor tube temperature sensor on the indoor panel: System doesn’t turn off, and the LED digital screen of the operation panel displays “E2”.
AUX air conditioner service manual PG motor feedback is abnormal Plastic temp. sensor is abnormal Copper temp. sensor is abnormal (indoor) Copper temp. sensor is abnormal (outdoor) Timing light twinkles 4 times in every 8 seconds Timing light twinkles 1 times in every 8 seconds Timing light twinkles 2 times in every 8 seconds Timing light twinkles 1 times in every 1seconds 1 2 3 4 9、H(Y) model air-conditioner fault display: Fault source Display mode PG motor feedback is abnormal Plastic temp.
AUX air conditioner service manual 12. Faults display of 18000BTU~24000BTU wall unit series air-conditioner: Fault source PG motor feedback is abnormal Plastic temp. sensor is abnormal Copper temp. sensor is abnormal (outdoor) Fault source PG motor feedback is abnormal Plastic temp. sensor is abnormal Copper temp.
AUX air conditioner service manual APPENDIX 2 Schematic Diagrams of some Controller Board 1. Schematic Diagram of Controller Board of E Series Air Conditioner with Display Screen (FUJITSU Chip) 1 2 3 4 5 6 CN9 1 FUSE 3.15A/250V CRV1 ZNR 1 104/275V 14K/681 2 X4 CN7 1 CN5 J? 2 1 CON2 CN1 A FAC 1.5U/450V BUZZER 1 220V-N RY4 RY3 + R37 +12V R38 510 R102 9 10 11 12 13 14 15 16 M C3021 IC7 BT136 0.
AUX air conditioner service manual 2. Schematic Diagram of Controller Board of EA Series Air Conditioner (Motorola Chip) 6 CN10 VH-3 R +5 ABCDEFG CN1 XH-10 - JHQ 8 DJR 6.3 T1 6.3 T2 6.3 CN9 Out Fan FAC 1.5U/450V 5 3 1 CN3 XH-3Ò£¿Ø Valve 1 3 COM1 COM2 COM3 Room Fan CN8 VH-5 7 DJR COMP L 1 5 1 4 1 3 1 2 1 3 1 N 1 2 3 R23 10K 1X7=470 R15 R16 R17 R18 R19 R20 R21 CRV2 0.
AUX air conditioner service manual 3. Schematic Diagram of Controller Board of HS Series Air Conditioner (Motorola Chip) 5 CN10 VH-5 COM1 COM2 COM3 R +5 STF 6.3 WFAN 6.3 1 2 3 4 5 6 7 8 9 10 11 12 13 R7 R8 R9 R10 R11 R12 R13 R45 10K 1X7=470 R101 Q5 Q4 9012 Z101 12V/1/2W Q6 9012 +5 9012 3W-11K CN9 T1 6.3 DJR ºì/ºÚÏß 1 3 T2 CN11 6.3 L N ºì/°×Ïß6.3 µç¼ÓÈÈÔ¤Áô 1 5 3 1 R103 CRV2 100-1/2w 0.1U/275V E101 R102 IC4 D101 470U/25V BT136 IN4007 3W-11K +5 8 COMP STF WFAN FAC 1.
AUX air conditioner service manual 4. Schematic Diagram of Controller Board of E Series Air Conditioner with Display Screen(with Renesas Chip) 1 2 3 4 5 6 7 8 CN10 VH-5A-3 1 VCC 5 3 1 FAC R9 R10 10K 10K IC3 104/63V 8 A0 Vcc 7 A1 WP 6 A2SCL 5 GND SDA CRV1 0.1u/250V/K 1 1.5u/450V D SCL SDA R101 1 2 TT IC7 BT136 D11 R102 3 VCC VCC NC 1 R36 10K IC6 SW 6*6*7 E5 100U/25V C13 104/63V D9 1N4007 R29 510R R33 0057U 4 22K VCC 2 1 15 3 14 4 13 5 12 6 11 7 10 8GND R8 5.
AUX air conditioner service manual APPENDIX 3 Conversion Table of Major Units 1. Conversion Table of Pressure Units Unit Pa kgf/cm2 Atm mmHg Psi Pa 1 1.02×10-5 9.87×10-6 7.5×10-3 1.450×104 kgf/cm2 9.8×104 1 9.68×10-1 7.36×102 1.421×109 Atm 1.013×105 1.033 1 7.6×102 mmHg 1.333×102 1.36×10-3 1.316×10-3 1 Psi 0.68948×104 7.0327×10-2 6.80517×10-2 51.711 2. Conversion of Energy Units 1kJ=1000J 1kcal=1000cal 1kcal=4.1868kJ 1BTU=0.252kcal=1.055kJ 1kcal=3.968BTU 1kJ=0.
AUX air conditioner service manual 4. Heat Conductivity Factors of Several Common Used Material Material λ(kJ/m·h·℃) Material λ(kJ/m·h·℃) Copper 1382 Cork 0.17-0.25 Aluminum 733 Air Interlayer 0.25 Steel 163 Water 2.1 Frosty layer 2.1 Glass 2.7-2.9 Fibre Glass 0.17-0.21 Saw Timber 0.25-0.34 Glass Cloth 0.13 Plywood 0.62-0.84 Slag Wool 0.21-0.34 Polyurethane Foam 0.042-0.11 5.
AUX air conditioner service manual Refrigeration 100 141 101 COP(%) 100 92.